MGE UPS Systems 6000 manual AC sources, Electrical characteristics

Page 6

MGETM GalaxyTM 6000 : Specification guide

Parallel UPS, three-phase, 250 to 3000 kVA*

* Power rating for an N+1 redundant configuration

3.5 - Limitation of harmonics upstream of the UPS

The UPS system shall not draw a level of harmonic currents that could disturb the upstream AC system, i.e. it shall comply with the stipulations of guide IEC 61000-3-4.

To that end, it shall be possible to equip each rectifier/charger input with a filter of the type …[compensated LC / non-compensated LC / with contactor / double-bridge / phase shifting]...

If necessary, it shall be possible to use an electronic active filtering system to obtain, at the normal AC input, the following levels, constant from 50% to 100% load:

ωtotal harmonic current distortion (THDI) upstream of the rectifier/charger not exceeding 4%;

ωinput power factor (pf) greater than 0.94.

3.6 - Efficiency

Overall efficiency shall be greater than or equal to:

ω95% at full rated load (In);

ω93% at half rated load (In/2).

3.7 - Noise level

The noise level for each unit, measured as per standard ISO 3746, shall be less than:

.........................................................................................................................................................................

ω69 dBA () for 250 and 300 kVA units).

ω72 dBA () for 400, 450, 500 and 600 kVA units).

.........................................................................................................................................................................

4 - AC sources

The UPS shall be designed to receive power from the sources listed below.

4.1 - Normal AC source

(rectifier input)

The normal AC source supplying the UPS shall, under normal operating conditions, have the following characteristics:

ωrated voltage: 380 - 400 or 415 volts rms at full rated load Pn;

ω voltage:

 

volts, ± 15%;

ωnumber of phases: 3 + N + earth;

ω frequency: Hz ± 10%.

4.2 - Bypass AC source

(static-bypass input, if separate from rectifier input)

The bypass power supplying the UPS in the event of an inverter shutdown (maintenance, failure) or an overload (short-circuit, heavy inrush currents, etc.) shall have the following characteristics:

ω voltage:

/

volts, ± 10%;

ωnumber of phases: 3 + N + earth; (a non-distributed neutral is possible);

ω frequency: Hz ± 5% (adjustable up to ± 2 Hz).

Outside these tolerances, it shall be possible to supply the load, but in downgraded mode.

5 - Electrical characteristics

5.1 - Rectifier and charger

5.1.1 - Supply

The rectifier and charger module shall be supplied via the normal AC input (see § 4. AC sources) and shall have the characteristics presented below.

5.1.2 - Inrush current

A device shall be provided to limit inrush currents.

When AC power fails and during genset start, the rectifier shall limit the power drawn to 70% of its rating for ten seconds. The remaining 30% shall be supplied by the battery.

5.1.3 - Battery-current limiting

For long battery life, an electronic device shall automatically limit the charging current to the maximum value

APC By Schneider Electric

Edition - 03/2009

Spec. E - 6

Image 6
Contents Power rating for an N+1 configuration Contents UPS definition Purpose Brief description Operating principle Sizing and general characteristics Electrical characteristics AC sourcesBatteries InverterStatic bypass Discrimination and short-circuit capacityMechanical characteristics Protection UPS not including batteryEnvironment conditions UPSDigital battery monitoring Battery managementMeasurement of actual backup time Self-testGraphic display User interface and communicationUser interface ControlsLocal and remote diagnostics and monitoring E. Services MaintainabilityCommunication Test procedures and quality system Standards and testsServices WarrantyInstallation services Electrical diagram UPSCentralized bypass UPS system with centralized bypass up to six unitsAppendix. Comparison table BatteryBattery management and protection Type of UPSEfficiency InverterStatic bypass User interfaceCertification ServicesCommunication Operation, Maintainability