MGE UPS Systems 6000 manual User interface and communication, Graphic display, Controls

Page 12

MGETM GalaxyTM 6000 : Specification guide

Parallel UPS, three-phase, 250 to 3000 kVA*

* Power rating for an N+1 redundant configuration

10 - User interface and communication

10.1 - User interface

UPS operation shall be facilitated by a user interface comprising:

ωa graphic display (at least quarter VGA and high resolution are preferable);

ωcontrols;

ωstatus indications with mimic panel.

10.1.1 - Graphic display

The graphic display shall facilitate operation by offering the functions listed below.

ω operating language

 

language all the operating information supplied on the

It shall be possible to display in the

 

screens.

 

 

ω step by step operating help

 

 

The graphic display shall assist the user by providing step by step help in the user's language.

ωanimated colour mimic diagram

The mimic diagram shall enable display of installation parameters, configuration, operating status and alarms and indication of operator instructions for switching operations (e.g. bypass).

ωdisplay of measurements

It shall be possible to display the following measurements:

-inverter output phase-to-phase voltages;

-inverter output currents;

-inverter output frequency;

-voltage across battery terminals;

-battery charge or discharge current;

-rectifier/charger input phase-to-phase voltages;

-rectifier/charger input currents;

-crest factor;

-active and apparent power;

-power factor of the load;

-battery temperature.

ωdisplay of status conditions and events

It shall be possible to display the following indications:

-load on battery power;

-load on UPS;

-load on automatic bypass;

-general alarm;

-battery fault;

-remaining battery backup time;

-low battery warning;

-bypass AC source outside tolerances;

-battery temperature.

Additional information shall be provided in view of accelerating servicing of the system, as specified in section 11 “Maintainability”.

ωdisplay of operating graphs

It shall be possible to display on the screen curves and bargraphs over significant periods for the measurements mentioned above.

ωlog of time-stamped events

This function shall store in memory and make available, for automatic or manually initiated recall, time-stamped logs of all important status changes, faults and malfunctions, complete with an analysis and display of troubleshooting procedures. It shall be possible to time stamp and store at least 3 000 events.

10.1.2 - Controls

The UPS shall comprise the following controls:

ωtwo ON and OFF buttons

Located on the front panel of the UPS, they shall control UPS-unit ON/OFF status.

It shall be possible to turn OFF the UPS externally via an isolated dry contact.

ωEPO terminal block

The UPS shall be equipped with an emergency power off terminal block for complete system shutdown following reception of an external control signal. The EPO command shall result in:

-shutdown of UPS units;

-opening of the static switch on the bypass line and of the battery circuit breaker;

-opening of an isolated dry contact on the programmable card.

ωalarm reset button

This button shall turn off audio alarms (buzzer) (see section 10.1.3). If a new alarm is detected after clearing the first, the buzzer sounds again.

APC By Schneider Electric

Edition - 03/2009

Spec. E - 12

Image 12
Contents Power rating for an N+1 configuration Contents UPS definition PurposeBrief description Operating principle Sizing and general characteristics Electrical characteristics AC sourcesBatteries InverterStatic bypass Discrimination and short-circuit capacityMechanical characteristics UPS not including battery Environment conditionsProtection UPSBattery management Measurement of actual backup timeDigital battery monitoring Self-testUser interface and communication User interfaceGraphic display ControlsLocal and remote diagnostics and monitoring E. Services MaintainabilityCommunication Test procedures and quality system Standards and testsServices WarrantyInstallation services Electrical diagram UPSCentralized bypass UPS system with centralized bypass up to six unitsBattery Battery management and protectionAppendix. Comparison table Type of UPSInverter Static bypassEfficiency User interfaceServices CommunicationCertification Operation, Maintainability