MGETM GalaxyTM 6000 : Specification guide
Parallel UPS, three-phase, 250 to 3000 kVA*
* Power rating for an N+1 redundant configuration
Appendix. Comparison table
Type of UPS
Total rated power (kVA) at PF 0.8
Manufacturer
Range of products
Operating mode (IEC
Parallel connection ≤ 4 modules without interrupting operation
kVA
| yes |
| no | |
kVA max. | yes |
|
| no |
|
Rectifiers
Frequency
Sinusoidal input current
Input power factor
No inrush or
Rapid battery charger
Voltage regulation
Independent regulation/monitoring systems
380 or 400 or 415 V ± 15 %
constant for loads with cos ϕ 0.8 lagging to cos ϕ 0.9 leading
50 or 60 Hz ± 10 %
THDI upstream ≤ 4 % with THM filter PF > 0.94
Backup time 10 minutes in t ≤ 11 hours, 4 hours in t ≤ 24 hours
± 1 %
yes yes
yes yes
yes yes yes
yes yes
no no
no no
no no no
no no
Battery
Type standard other
Service life
Backup time
sealed lead acid in a cabinet | yes | |
|
| yes |
|
| |
| years | yes |
| ||
| minutes | yes |
|
no no no no
Battery management and protection
Temperature correction |
| yes |
Measurement of actual backup time, | load, temperature, age | yes |
depending on: |
|
|
Cold start on battery power |
| yes |
Protection against deep discharge | with | yes |
0.05 C10 to 0.1 C10 (depending on the | yes | |
| battery) |
|
no no
no no no
yes | |
Calculation of real backup time | yes |
Block by block monitoring | yes |
no no no
APC By Schneider Electric | Edition - 03/2009 | Spec. E - 18 |