MGE UPS Systems Pulsar EX 1500, Pulsar EX 700 user manual Operation, Start-up, Bargraph indications

Page 17

3. Operation

3.1 Start-up

The protected equipment connected to the UPS can be energised, whether AC input power is available or not.

21

22

23

Press the ON / OFF button 23 .

The buzzer beeps and all the LEDs go ON.

The buzzer beeps twice, then:

-If AC input power is available, LED 21 goes ON, indicating operation in ON-LINE mode.

-If AC input power is not available and the UPS is configured for automatic restart mode, the buzzer beeps three times and LED 22 goes ON, signalling operation on battery power.

All connected equipment is energised.

If LEDs 21 or 22 do not go ON or if LEDs 12 to 14 flash, there is a fault (see section 4.1).

3.2 Bargraph indications

%

100%

80%

50%

20%

%

test

1

2

by-pass

12

13

14

15

16

18

19

LEDs 12 to 15 provide three different indications:

1 - Remaining backup time in percent (during normal operation).

2 - Percent load drawn by the protected equipment, when button 16 is pressed.

3 - Operating faults (flashing LED and beeps):

Ê12 Overload.

Ê13 UPS fault.

Ê14 Battery fault.

Status LEDs 18 and 19 for programmable outlets 1 and 2:

-LEDs OFF: the outlets are not supplied with power.

-LEDs flashing: status change in progress.

-LEDs ON: the outlets are supplied with power.

Outlets 1 and 2 can be remotely programmed and controlled. They may be used for sequential start-up of the protected applications, shedding of non-priority applications during operation on battery power, and priority management at the end of battery backup time to reserve the longest possible backup time for the most sensitive applications. These outlets are programmed using Solution Pac software.

51031604EN/AA - Page 17

Image 17
Contents Pulsar EX Introduction Safety rules SafetySafety of persons Product safetyPictograms Using this documentForeword Contents Shutdown Environment AppendicesTower model Rack model PresentationPulsar EX range Tower model BackPulsar EX 700 / Pulsar EX Pulsar EXUSB 20% Control panelUnpacking and checks Installation12 51031604EN/AA Rack mounting diagram with rails Installation of the rack versionConnection to the RS 232 or USB communications port optional Installation of the communications-card option Connections Start-up OperationBargraph indications LEDs 12 to 15 provide three different indicationsThreshold for the low-battery warning Transfer to battery powerEnd of backup time Sleep modePersonalisation optional Battery tabFunction On / OFF conditions tabBypass tab ShutdownOutput tab Troubleshooting MaintenanceSafety rules Replacement of the battery moduleRemoval of battery module Reinstallation of the battery moduleRack model Environment UPS recycling at the end of service lifeThis product has been designed to respect the environment PackingAppendices Technical characteristicsSimplified diagram Operating conditions UPS GlossaryConnection Index28 51031604EN/AA