American Power Conversion MX28B600 Apply AC Power, System Parameters Verification/Adjustment

Page 24

MX28B600-48V

5.9.1 Apply AC Power

Turn on the circuit breakers that supply AC power to the rectifiers in the MX28B600 DC power plant. The main screen should appear on the control unit display (see Figure 5.9-1). The display on the control unit is a 2-lines by 16-characters display. The cursor cycles below the characters of the active selection on the display. Information shown in the second line of Figure 5.9-1 that extends beyond 16 characters (to the right of the “S” in “ALARMS”) can viewed on the control unit display by using the scrolling controls (refer to Section 6 for operation of the control unit).

NOTE: When AC power is initially applied, there is a 60-second period during which no alarms are reported.

MX28B600 +

STATUS ALARMS SYSTEM MODULES BATT PIN OEM

Figure 5.9-1

5.9.2 System Parameters Verification/Adjustment

The MX28B600 system control unit is delivered with pre-programmed parameter default settings. A complete listing and description of all system configuration parameters as well as displayable system status and information is provided in Section 6. Read Section 6 to gain an understanding of and how to use the operational features provided by the MX28B600 DC power plant. As a minimum, the following parameters should be verified and adjusted, if required, before connecting batteries or loads to the power plant:

1)Battery Float Voltage - default = -54.00V DC (Check the manufacturer’s recommendation for the batteries being used in the system.)

2)Battery Maximum Recharge Rate - default = 50A. (Bellcore specifications recommend a maximum charging rate of capacity (in Ampere-hours) divided by 20 hours; check the battery manufacturer’s recommendation.)

3)System Voltage - measurement -54.00V DC (This is a measurement by the system of the DC output bus voltage.)

4)LVD Option - default = “Enable” (If the MX28B600 does not have an LVD installed, this should be changed to “Disable”.)

5)Rectifier Information - Check the rectifier information displays to verify that all rectifiers installed can be viewed on the control unit display and that no rectifier alarms are active.

Section 6 provides location information for these parameters and how to make changes if required.

5.9.3 Full System Power Up

To complete a full system power up, perform the following steps

1)Turn OFF all the circuit breakers that supply AC power to the rectifiers in the MX28B600 DC power plant.

2)Turn on the external circuit breaker from the battery to the power plant.

20

Image 24
Contents MX28B600 Revision History Table of Contents Product Overview and Technical DescriptionMX28B600 General Information IntroductionInspection upon Receipt of Goods General Visible External DamageConcealed Damage Customer Service and Support Warranty Provisions Warranty ReturnsWarranty Repair or Replacement General ProvisionsMX28B600 1. MX28B600 Description2. MX28B600 Block Diagram Power Output Capacity RectifiersControl Unit AC Input Power Battery connectionsDC Distribution MountingEnvironmental Mechanical ComplianceInstallation Procedures Preparation Recommended ToolsRecommended Test Equipment Equipment InspectionBattery Connections VentilationConnecting the Cables Alarm ConnectionsCable Sizing Considerations 1. External Alarm Input Definition 2. External Alarm Input ConnectionsAlarm Outputs Alarm Terminal Output Designation User Alarm Notes NO-NC-C1. Plug-in Circuit Breakers 2. GMT FusesReattach the circuit breaker cover panel Battery Temperature Probe Installation Power-Up and CheckoutLoad Connections Circuit Breakers Apply AC Power System Parameters Verification/AdjustmentFull System Power Up MX28B600-48V SETUP, ADJUSTMENTS, and Operation User InterfaceSnmp interface Alarm Output Relays Parameter Locations, Descriptions, and Default Values0000 11112222 OEM R OffsetDisplay Type 000255Date JUN 27Test Relay Test Min RlyTest Maj Rly Batt FloatBatt Disc Alm m+ Batt HV AlmBatt LV Alm Batt HT AlmRect FF Alm Rect RFA AlmCir Bkr 48VFuse 1 Alm Fuse 16 AlmIn-Rly Input RelayLVD1 Reset LVD2 ResetEnable Relay MajorMX28B600-48V 1. Control Unit Menu Structure 1. Control Unit Menu Structure Modules Rect SET-ALM Alias Fuse LVD SET-ALM

MX28B600 specifications

The American Power Conversion (APC) MX28B600 is a top-of-the-line uninterruptible power supply (UPS) designed to provide reliable power protection for a variety of applications. Known for its robust features and advanced technologies, the MX28B600 is an ideal solution for small to medium-sized data centers, telecommunications systems, and other critical IT infrastructure.

One of the standout features of the MX28B600 is its high capacity, which allows it to support a wide range of devices while accommodating future growth. With a power rating of 28 kVA, it can effectively handle multiple servers and network equipment without compromising performance. This capacity ensures business continuity even during power outages, surges, or fluctuations.

The MX28B600 utilizes advanced Double Conversion Online technology, which provides consistent and clean power to connected equipment. This technology ensures that the output voltage is tightly regulated, protecting sensitive electronics from damage and improving overall reliability. Additionally, the UPS features a wide input voltage range, allowing it to function effectively even in unstable power environments.

Another critical characteristic of the MX28B600 is its modular design, which provides flexibility for customization and scalability. Users can easily add or remove modules based on their evolving power requirements, making it a cost-effective solution over time. This modularity also simplifies maintenance and reduces downtime, ensuring that businesses can remain operational without interruptions.

The APC MX28B600 incorporates a user-friendly interface that makes monitoring and managing power needs straightforward. Its LCD display provides real-time information on battery status, output power, and alerts, allowing users to make informed decisions quickly. Additionally, the UPS is equipped with Remote Manager capabilities, enabling remote monitoring and management from any location, which is especially beneficial for IT administrators responsible for multiple sites.

Designed with energy efficiency in mind, the MX28B600 meets stringent environmental standards. Its Eco mode and Intelligent Battery Management system optimize battery life, reduce energy costs, and lower carbon emissions, contributing to a more sustainable operation.

In conclusion, the APC MX28B600 is an exceptional choice for businesses looking for reliable and efficient power protection. With its high capacity, advanced technologies, modular design, and energy-efficient operation, it is poised to meet the demands of modern organizations while ensuring continuous uptime and protecting critical equipment.