American Power Conversion MX28B600 manual DC Distribution, Mounting, Environmental

Page 14

MX28B600-48V

4.7DC Distribution

Two plug-in circuit breaker tiers, consisting of a 24-position panel and two 10-position panels, provide 43 positions of -48V distribution. One position is reserved for the Manual Battery Disconnect Switch. The breaker tiers are center fed via bus bars to the -48V DC bus with each side having an ampacity of 300A.

Connections for -48V DC loads, requiring standard #10-32 two-hole lugs on 5/8-inch centers, are located directly above the corresponding breaker. The load returns connect to the return bus, which accommodates 24 two-hole #10-32 lugs on 5/8-inch centers, and four two-hole ¼”-20 lugs on ¾-inch centers. The return bus also provides a pair of threaded 3/8”-16 holes on 1-inch centers for connection of a cable to the master station ground. Figure 4.7-1shows the power plant’s DC distribution section with the front cover removed.

Eight GMT fused outputs are also available as an option, and are configured at the factory.

Figure 4.7-1. Upper Tier DC Distribution (Front Cover Removed)

4.8Mounting

Front mounting on standard 72” or 84” high, 23-inch rails

4.9Environmental

Ambient Temperature: -20°C to +65°C (-4°F to +149°F) operating -40°C to +85°C (-40°F to +185°F) storage

Humidity: 0% to 85% RH non-condensing operating

0% to 95% RH non-condensing storage

Altitude: Up to 3000m (9800Ft) operating Up to 10,000m (32,000Ft) storage

10

Image 14
Contents MX28B600 Revision History Table of Contents Product Overview and Technical DescriptionMX28B600 Inspection upon Receipt of Goods General General InformationIntroduction Visible External DamageConcealed Damage Customer Service and Support Warranty Repair or Replacement Warranty ProvisionsWarranty Returns General ProvisionsMX28B600 1. MX28B600 Description 2. MX28B600 Block Diagram Control Unit Power Output CapacityRectifiers AC Input Power Battery connectionsEnvironmental DC DistributionMounting Mechanical ComplianceRecommended Test Equipment Installation ProceduresPreparation Recommended Tools Equipment InspectionBattery Connections VentilationCable Sizing Considerations Connecting the CablesAlarm Connections 1. External Alarm Input Definition 2. External Alarm Input ConnectionsAlarm Outputs Alarm Terminal Output Designation User Alarm Notes NO-NC-C1. Plug-in Circuit Breakers 2. GMT FusesReattach the circuit breaker cover panel Load Connections Circuit Breakers Battery Temperature Probe InstallationPower-Up and Checkout Full System Power Up Apply AC PowerSystem Parameters Verification/Adjustment MX28B600-48V Snmp interface SETUP, ADJUSTMENTS, and OperationUser Interface Alarm Output Relays Parameter Locations, Descriptions, and Default Values2222 00001111 OEM R OffsetDate Display Type000255 JUN 27Test Maj Rly Test RelayTest Min Rly Batt FloatBatt LV Alm Batt Disc Alm m+Batt HV Alm Batt HT AlmCir Bkr Rect FF AlmRect RFA Alm 48VIn-Rly Fuse 1 AlmFuse 16 Alm Input RelayEnable LVD1 ResetLVD2 Reset Relay MajorMX28B600-48V 1. Control Unit Menu Structure 1. Control Unit Menu Structure Modules Rect SET-ALM Alias Fuse LVD SET-ALM