5.7.2 Installation of Circuit Breakers and Fuses

5.7.2.1Plug-in Circuit Breakers

1)Remove the circuit breaker cover panel and the plastic cover(s)/insert(s) from the desired location(s).

2)Install the circuit breaker(s) by snapping the top terminal onto the upper bus bar and rotating the unit down until the second terminal snaps onto the breaker termination post as shown in Figure 5.7-1. The breaker alarm terminals are designed to make contact with the alarm terminal board as the breaker is snapped into place.

NOTE: Circuit breaker alarm contacts close when the circuit breaker is tripped but not when it is turned OFF.

***** CAUTION *****

During circuit breaker installation, carefully align the breaker alarm terminals with the alarm terminal board to avoid breaker terminal damage.

3) Reattach the circuit breaker cover panel.

Figure 5.7-1. Installation of Circuit Breakers

5.7.2.2 Optional GMT Fuses

Fuseholders that accommodate GMT fuses are located on the interface card mounted in the top left side of the unit. These fuseholders are only connected to -48V DC if the system has been purchased with the GMT fuse option. This option supplies -48V DC to the fuseholders through

18

Image 22
Contents MX28B600 Revision History Table of Contents Product Overview and Technical DescriptionMX28B600 Inspection upon Receipt of Goods General General InformationIntroduction Visible External DamageConcealed Damage Customer Service and Support Warranty Repair or Replacement Warranty ProvisionsWarranty Returns General ProvisionsMX28B600 1. MX28B600 Description2. MX28B600 Block Diagram Rectifiers Power Output CapacityControl Unit AC Input Power Battery connectionsMounting DC DistributionEnvironmental Mechanical ComplianceRecommended Test Equipment Installation ProceduresPreparation Recommended Tools Equipment InspectionBattery Connections VentilationAlarm Connections Connecting the CablesCable Sizing Considerations 1. External Alarm Input Definition 2. External Alarm Input ConnectionsAlarm Outputs Alarm Terminal Output Designation User Alarm Notes NO-NC-C1. Plug-in Circuit Breakers 2. GMT FusesReattach the circuit breaker cover panel Power-Up and Checkout Battery Temperature Probe InstallationLoad Connections Circuit Breakers System Parameters Verification/Adjustment Apply AC PowerFull System Power Up MX28B600-48V User Interface SETUP, ADJUSTMENTS, and OperationSnmp interface Alarm Output Relays Parameter Locations, Descriptions, and Default Values2222 00001111 OEM R OffsetDate Display Type000255 JUN 27Test Maj Rly Test RelayTest Min Rly Batt FloatBatt LV Alm Batt Disc Alm m+Batt HV Alm Batt HT AlmCir Bkr Rect FF AlmRect RFA Alm 48VIn-Rly Fuse 1 AlmFuse 16 Alm Input RelayEnable LVD1 ResetLVD2 Reset Relay MajorMX28B600-48V 1. Control Unit Menu Structure 1. Control Unit Menu Structure Modules Rect SET-ALM Alias Fuse LVD SET-ALM