American Power Conversion LVD300, LVD400, LVD500, LVD600, LVD1000 manual Specification

Page 5

SECTION 2: SPECIFICATION

INPUT

1 The input voltage is -54.5 V dc nominal from an external power system.

OUTPUT

2 The output voltage is -54.5 V dc nominal.

MECHANICAL

3The units are housed in grey plastic boxes of dimensions 366mm wide x 193 mm deep x 470mm high. External busbars for input and output connections are provided on 15000264.

WEIGHT

4 The weight of the units are 15 kg.

OPERATIONAL TEMPERATURE

5 The operational temperature is -5 °C to +50 °C.

OPERATIONAL HUMIDITY

6 The operational relative humidity is 5% to 95% non-condensing.

SAFETY STANDARDS

7The units are for use in conjunction with telecommunications apparatus and are designed to meet the standard BS EN 60950 specification for safety of information technology equipment, including electrical business equipment.

ALARMS

8One set of volt free change over contacts are provided on a terminal block (TB1) to indicate the state of the contactor.

9The input and output sides of the fuse can be monitored via a 27kresistor on TB2

Text artwork 990-9030 Rev. A. Equipment Handbook for the Low Voltage Disconnectors series

Page 5 of 20

Image 5
Contents Equipment Handbook for LOW Voltage Disconnectors Contents Issue Description Date Issue RecordBefore using the units, carry out the following Safety InstructionsSpecification Circuit Description LVD PCA LED Controls and IndicatorsKeyswitch PRE Installation Test Installation and CommissioningVoltage Monitor Settings Stage 3 Remote loop connections Stage 2 Input connectionsCommissioning Stage 2 Power up sequenceStage 1 Preparation Stage 3 Output connectionsAnnual Check Routine MaintenanceSIX Monthly Check Field Replaceable Units Fault Diagnosis and RepairFuse Failure Fuse Removal and ReplacementContactor Failure LVD PCA Removal and ReplacementLVD PCA Failure Contactor Removal and Replacement Method Manual HandlingPreparation Date Service LOG Action Actioned by Name Signature Appendix a Service LOGBlank Drawing Appendix B System DrawingsRear