American Power Conversion LVD300, LVD400, LVD500, LVD600, LVD1000 manual Stage 2 Input connections

Page 9

INSTALLATION

WARNINGS

(1)THIS APPARATUS MUST BE INSTALLED BY A PROFESSIONAL INSTALLER. WHEN INSTALLED, A PROTECTIVE EARTH MUST BE PROVIDED FOR SAFETY, IN ACCORDANCE WITH BS6701: PART 1:1990: CLAUSE 6.10.

'WARNING: THE PROTECTIVE EARTH CONNECTION MUST BE HARD WIRED.'

(2)EXERCISE EXTREME CAUTION WHEN WORKING OR MAKING MEASUREMENTS WITHIN THE UNITS. HIGH VALUE DC VOLTAGES MAY PRESENT A HAZARD OWING TO THE DANGER OF SHORT CIRCUITS. RINGS, WATCHES AND JEWELLERY SHOULD BE REMOVED AND ONLY INSULATED TOOLS SHOULD BE USED. A SOLDERING IRON SHOULD NOT BE USED UNLESS THE INPUT AND OUTPUT HAVE FIRST BEEN ISOLATED.

(3)THESE UNITS USE POSITIVE EARTH. CAREFULLY OBSERVE THE CORRECT POLARITY WHEN CONNECTING THE UNITS.

(4)LIVE WORKING MUST NOT BE CARRIED OUT ON THE UNITS UNLESS ABSOLUTELY NECESSARY. A CERTIFICATE OF LIVE WORKING MUST BE OBTAINED BY THE PERSONNEL INVOLVED BEFORE ANY LIVE WORKING IS COMMENCED.

(5)REFER TO MANUAL HANDLING, SECTION 8, BEFORE ATTEMPTING TO LIFT OR MOVE THE UNITS. Stage 1 - Unpacking

4Unpack the unit and check that the unit is present and undamaged and includes a handbook and factory completed test certificate.

Stage 2 - Input connections

5To connect the dc input cables to the unit, proceed as follows:

5.1Mount the unit on a suitable wall using the mounting hole on each corner.

5.2Ensure that the external power system intended for connection to the unit is switched off.

5.3Open the door, remove five screws and washers on the plastic plate and lift off the plate.

5.4Remove the circular plate from the bottom and feed the negative and auxiliary positive common input cables from the external power system into the unit.

5.5Connect the negative cable to either the internal negative input plate (for 15000218 and 15000248) or the external NEGATIVE IN busbar (for 15000264). Note that the unit does not require a positive common input cable.

5.6Connect the auxiliary positive common cable (to power the LVD PCA) to the AUX. terminal on TB1 (terminal 3).

Stage 3 - Remote loop connections

6If required, remove the link from the REMOTE LOOP terminals on TB1 (terminals 1 and 2) and make connections to the terminals from a remote location.

Text artwork 990-9030 Rev. A. Equipment Handbook for the Low Voltage Disconnectors series

Page 9 of 20

Image 9
Contents Equipment Handbook for LOW Voltage Disconnectors Contents Issue Description Date Issue RecordBefore using the units, carry out the following Safety InstructionsSpecification Circuit Description Controls and Indicators KeyswitchLVD PCA LED Installation and Commissioning Voltage Monitor SettingsPRE Installation Test Stage 3 Remote loop connections Stage 2 Input connectionsCommissioning Stage 2 Power up sequenceStage 1 Preparation Stage 3 Output connectionsRoutine Maintenance SIX Monthly CheckAnnual Check Field Replaceable Units Fault Diagnosis and RepairFuse Failure Fuse Removal and ReplacementLVD PCA Removal and Replacement LVD PCA FailureContactor Failure Contactor Removal and Replacement Manual Handling PreparationMethod Date Service LOG Action Actioned by Name Signature Appendix a Service LOGBlank Drawing Appendix B System DrawingsRear