American Power Conversion AP9312TH Connection process overview Connecting dry contact devices

Page 10

Installation, continued

Connection process: overview

Connecting dry contact devices

You must perform two procedures to set up contact monitoring.

See “Contact Sensors” on page 7 to select and connect contact sensors.

See “Connecting dry contact devices” on this page.

To connect dry contact devices to the Environmental Monitoring Unit:

1.Connect contact closure sensors to the removable screw terminal block as described in “Contact Sensors” starting on page 7.

2.The connector accepts wire sizes from 14 AWG (1.6 mm2) to 26 AWG (0.4 mm2). Remove 0.25" (6 mm) of

the wire’s insulation.

3.Connect the screw terminal block to the unit’s Sensor Zones connector.

Following is an example of a completed installation:

To complete the setup, see “Quick Configuration” on page 11.

6

Image 10
Contents Environmental Monitoring Unit Page Contents Maintenance Correcting problems If problems persist Introduction Product inventory Snmp Installation Attach the assembly tightly to the enclosure using four Connection process overview Connecting dry contact devices Contact Sensors Sensor Zones Connector Pinout Pin FunctionSensors in parallel and normally closed sensors in series Example of a typical hookup Quick Configuration Through the Management Card Wizard.On next Over the Network by ARP. To configure the Environmental Through a Web browser Through TelnetWarranty Information Possibility of such damageTroubleshooting Problem Possible Cause SolutionIf a problem is not mentioned in Correcting problems on Specifications SpecificationApproval Life-Support Policy Declaration of Conformity APC Worldwide Customer Support