American Power Conversion AP7902 AP7911 quick start How to Recover From a Lost Password

Page 20

How to Recover From a Lost Password

You can use a local computer, a computer that connects to the Rack PDU or other device through the serial port to access the control console.

1.Select a serial port at the local computer, and disable any service that uses that port.

2.Connect the APC smart-signaling cable (940-0144) to the selected port on the computer and to the serial port at the Rack PDU:

3.Run a terminal program (such as HyperTerminal®) and configure the selected port as follows:

9600 bps

8 data bits

no parity

1 stop bit

no flow control.

4.Press ENTER, repeatedly if necessary, to display the User Name prompt. If you are able to display the User Name prompt, verify the following:

The serial port is not in use by another application

The terminal settings are correct as specified in step 3

The correct cable is being used as specified in step 2

5.Press the Reset button. The Status LED will flash between red or orange and green. Press the Reset button a second time immediately while the LED is flashing to reset the user name and password to their defaults temporarily.

6.Press ENTER as many times as necessary to redisplay the User Name prompt, then use the default, apc, for the user name and password. (If you take longer than 30 seconds to log on after the User Name prompt is redisplayed, you must repeat step 5 and log on again.)

7.From the Control Console menu, select System, then User Manager.

8.Select Administrator, and change the User Name and Password settings, both of which are now defined as apc.

9.Press CTRL-C, log off, reconnect any serial cable you disconnected, and restart any service you disabled.

16

Switched Rack PDU Installation and Quick Start

Image 20
Contents Switched Rack Power Distribution Unit Page Contents How to Download Firmware Updates Specifications AP7911 Product Description and InventoryAP7902 Additional DocumentationInventory Receiving inspectionHow to Install the Rack PDU Mounting options How to Install the Rack PDU Operation Display interfaceQuick Configuration IP address of the Rack PDU Subnet mask Default gatewayTCP/IP configuration methods InfraStruXure Manager’s documentation for moreBootp the default setting ConfigurationSettings are Manual, Dhcp only, Bootp only, and Dhcp Quick Configuration Option 43 = 01 04 31 41 50 43 where Control console Local access toRemote access to Choose Network from the Control Console menu Overview Web interfaceTelnet/SSH Environment of SSL and SSH. Administrators can disable If you enable SSL and SSH, disable FTP. Allowing fileTransfers using FTP compromises the high security How to Recover From a Lost Password How to Download Firmware Updates XmodemSpecifications AP7902/AP7911Warranty and Service Limited warrantyWarranty limitations Obtaining serviceLife-Support Policy General policyExamples of life-support DevicesRadio Frequency Interference Changes or modifications to this unit notExpressly approved by the party Responsible for compliance could void990-1664