THIRD PARTY BATTERY SOLUTION

Batteries must be Sealed Lead-Acid type. Use 50 A, 250 VDC fuses with an Interrupt rating of

20,000 A.

Ensure that the external batteries are wired prior to connecting the batteries to the UPS.

If using a non-APC battery pack, a 192 V battery string should be wired to the UPS using the enclosed battery cable assembly.

Connect the Ground and Wire the Battery System

1.Connect the ground wire (included), to the battery enclosure ground and the TVSS screw on the back of the UPS.

2.Cut off one of the connectors on the cable revealing positive and negative wires.

3.Connect the positive (red), and negative (black) wires to the positive and negative terminals on the external battery system. Ensure that the proper polarities are connected.

4.Plug the cable connector into one of the battery connector receptacles on the back of the UPS. Either receptacle may be used.

5

Image 7
Contents APC Smart-UPSRT UXI/UXICH Page Introduction Page Normal bypass Battery Safety Connect the Ground and Wire the Battery System Avoid using extension cords Operation Cold Start User Configurable Items Function Factory User Selectable Description Default Choices Connect the EPO Emergency Power OFF Option 3000/5000 VA models Battery Replacement Service Troubleshooting Bypass LED Illuminates Regulatory Agency Approvals and Radio Frequency Warnings Declaration of Conformity APC Worldwide Customer Support

RT-UXI, RT-UXICH specifications

American Power Conversion (APC) has long been a leader in power protection and management solutions, and its RT-UXICH and RT-UXI line of uninterruptible power supplies (UPS) exemplifies the company's commitment to reliability and innovation. These UPS units are specifically designed to safeguard critical equipment in data centers, telecommunications systems, and other applications where power continuity is essential.

One of the main features of the RT-UXICH and RT-UXI is their advanced double-conversion technology. This allows for a consistently clean and stable output voltage, ensuring that sensitive electronic equipment is protected from voltage fluctuations and power surges. The double-conversion design also means that the UPS can provide power instantaneously during an outage, eliminating any downtime for connected devices.

Both models are equipped with a high-efficiency operation mode which contributes to reduced energy consumption, making them environmentally friendly options for businesses looking to optimize their energy use. The digital signal processing technology used in these models enhances performance and reliability, ensuring that power management is both efficient and effective.

The RT-UXICH and RT-UXI also feature hot-swappable battery modules, enabling users to replace batteries without shutting down critical loads. This capability is crucial for mission-critical environments where uptime is non-negotiable. Moreover, the intuitive LCD interface provides real-time monitoring and alerts, allowing users to easily assess the UPS status and make informed decisions quickly.

In terms of connectivity, these units come with multiple communication ports including USB and serial communication options, enabling seamless integration with existing management software. Additionally, they support network management cards that allow remote monitoring and management of the UPS, ensuring that any potential issues can be addressed promptly.

Compliance with various international safety and environmental standards solidifies the reliability of these units. APC also provides robust support and warranty options, further enhancing peace of mind for businesses investing in power protection.

Overall, the APC RT-UXICH and RT-UXI UPS models are characterized by their reliability, efficiency, and advanced technology features, making them ideal solutions for organizations that demand uninterrupted power supply for their crucial operations.