American Power Conversion RT-UXICH user manual User Configurable Items

Page 11

USER CONFIGURABLE ITEMS

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

Automatic Self-Test

Every 14 days

Every 7 days(168 hours),

Set the interval at which the

 

(336 hours)

14 days (336 hours)

UPS will execute a self-test.

 

 

On Startup Only,

 

 

 

No Self-Test

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight characters to

Uniquely identify the UPS, (i.e.

 

 

define the UPS

server name or location) for

 

 

 

network management purposes.

 

 

 

 

Date of Last Battery

Manufacture Date

Date of

Reset this date when you replace

Replacement

 

Battery Replacement

the battery module.

 

 

mm/dd/yy

 

 

 

 

 

Minimum Capacity

0 percent

0, 15, 25, 35, 50, 60, 75,

Following a low-battery

Before Return from

 

90 percent

shutdown, the batteries will be

Shutdown

 

 

charged to the specified

 

 

 

percentage before powering

 

 

 

connected equipment.

 

 

 

 

Alarm Delay After

5 second delay

5 or 30 second delay

Mute ongoing alarms or disable

Line Failure

 

At Low Battery

all alarms permanently.

 

 

Never

 

 

 

 

 

Shutdown Delay

20 seconds

0, 20, 60, 120, 240, 480,

Set the interval between the time

 

 

720, 960 seconds

when the UPS receives a

 

 

 

shutdown command and the

 

 

 

actual shutdown.

 

 

 

 

Duration of

2 minutes

2, 5, 7, 10, 12, 15, 18,

The low battery warning beeps

Low Battery Warning.

PowerChute

20 minutes

are continuous when two

 

 

minutes of run time remain.

 

software provides

 

 

automatic,

 

Change the warning interval

 

unattended

 

default to a higher setting if the

 

shutdown when

 

operating system requires a

 

approximately 2

 

longer interval for shutdown.

 

minutes of battery

 

 

 

operated runtime

 

 

 

remains.

 

 

 

 

 

 

Synchronized Turn-on

0 seconds

0, 20, 60, 120, 240, 480,

The UPS will wait the specified

Delay

 

720, 960 seconds

time after the return of utility

 

 

 

power before turn-on (to avoid

 

 

 

branch circuit overload).

 

 

 

 

9

Image 11
Contents APC Smart-UPSRT UXI/UXICH Page Introduction Page Normal bypass Battery Safety Connect the Ground and Wire the Battery System Avoid using extension cords Operation Cold Start User Configurable Items Function Factory User Selectable Description Default Choices Connect the EPO Emergency Power OFF Option 3000/5000 VA models Battery Replacement Service Troubleshooting Bypass LED Illuminates Regulatory Agency Approvals and Radio Frequency Warnings Declaration of Conformity APC Worldwide Customer Support

RT-UXI, RT-UXICH specifications

American Power Conversion (APC) has long been a leader in power protection and management solutions, and its RT-UXICH and RT-UXI line of uninterruptible power supplies (UPS) exemplifies the company's commitment to reliability and innovation. These UPS units are specifically designed to safeguard critical equipment in data centers, telecommunications systems, and other applications where power continuity is essential.

One of the main features of the RT-UXICH and RT-UXI is their advanced double-conversion technology. This allows for a consistently clean and stable output voltage, ensuring that sensitive electronic equipment is protected from voltage fluctuations and power surges. The double-conversion design also means that the UPS can provide power instantaneously during an outage, eliminating any downtime for connected devices.

Both models are equipped with a high-efficiency operation mode which contributes to reduced energy consumption, making them environmentally friendly options for businesses looking to optimize their energy use. The digital signal processing technology used in these models enhances performance and reliability, ensuring that power management is both efficient and effective.

The RT-UXICH and RT-UXI also feature hot-swappable battery modules, enabling users to replace batteries without shutting down critical loads. This capability is crucial for mission-critical environments where uptime is non-negotiable. Moreover, the intuitive LCD interface provides real-time monitoring and alerts, allowing users to easily assess the UPS status and make informed decisions quickly.

In terms of connectivity, these units come with multiple communication ports including USB and serial communication options, enabling seamless integration with existing management software. Additionally, they support network management cards that allow remote monitoring and management of the UPS, ensuring that any potential issues can be addressed promptly.

Compliance with various international safety and environmental standards solidifies the reliability of these units. APC also provides robust support and warranty options, further enhancing peace of mind for businesses investing in power protection.

Overall, the APC RT-UXICH and RT-UXI UPS models are characterized by their reliability, efficiency, and advanced technology features, making them ideal solutions for organizations that demand uninterrupted power supply for their crucial operations.