Configuration Settings

Configuration Settings

Settings are adjusted through PowerChute software, optional SmartSlot accessory cards, or in terminal mode.

Function

Factory

User Selectable

Description

Default

Choices

 

 

 

 

 

 

Automatic

Every 14 days

• Every 7 days

Set the interval at which the UPS will execute a

Self-Test

(336 hours)

(168 hours)

 

self-test.

 

 

• Every 14 days

 

 

 

(336 hours)

 

 

 

 

• On start up only

 

 

 

• No self-test

 

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight characters

Uniquely identify the UPS, (i.e. server name or

 

 

(alphanumeric)

location) for network management purposes.

 

 

 

 

 

Date of Last

Manufacture

mm/dd/yy

 

Reset this date when you replace the battery

Battery

Date

 

 

module.

Replacement

 

 

 

 

 

 

 

 

 

Minimum

0 percent

• 0%

• 60%

Specify the percentage to which batteries will be

Capacity Before

 

• 15%

• 75%

charged following a low battery shutdown before

Return from

 

• 30%

• 90%

powering connected equipment.

Shutdown

 

 

 

• 45%

 

 

 

 

 

 

 

 

 

 

 

Alarm Delay

Enable

• Enable

• Disable

Mute ongoing alarms or disable all alarms

 

 

• Mute

 

permanently.

 

 

 

 

 

Shutdown Delay

90 seconds

• 0 s

• 360 s

Set the interval between the time when the UPS

 

 

• 90 s

• 450 s

receives a shutdown command and actual

 

 

• 180 s

• 540 s

shutdown.

 

 

• 270 s

• 630 s

 

 

 

 

 

 

Low Battery

2 minutes

• 2 m

• 14 m

PowerChute software interface provides

Warning

 

• 5 m

• 17 m

automatic, unattended shutdown when

 

 

• 8 m

• 20 m

approximately two minutes of battery operated

 

 

run time remains.

 

 

• 11 m

• 23 m

 

 

The low-battery warning beeps are continuous

 

 

 

 

 

 

 

 

when two minutes of run time remain.

 

 

 

 

Change the low battery warning interval setting to

 

 

 

 

the time that the operating system or system

 

 

 

 

software requires to safely shut down.

 

 

 

 

 

Synchronized

0 seconds

• 0 s

• 240 s

Specify the time the UPS will wait after the return

Turn-on Delay

 

• 60 s

• 300 s

of utility power before start up (to avoid branch

 

 

• 120 s

• 360 s

circuit overload).

 

 

• 180 s

• 420 s

 

 

 

 

 

 

10

Smart-UPS RT 2400/3000 VA Tower/Rack-Mount UPS User Manual

Image 10
Contents APC Smart-UPS Page Unpacking and Equipment Placement Introduction/Before InstallationContact Information Safety Information About this ManualTo Install the UPS in a Tower Configuration InstallationTo Install the UPS in a Rack To Install the UPS with External Battery PacksConnectors Type Description Connect the Battery and Install the Front Bezel If Required, Connect the Emergency Power Off EPO FeatureConnect Power and Start Up the UPS Terminal Mode Configuration For Additional Computer System SecurityOperation Display Panel IndicatorsDisplay Panel Display Panel Functions On Battery OperationUtility Voltage Measurement Configuration Settings UPS ID UpsidenFunction Factory User Selectable Description Default Choices To Install a Replacement Battery Storage, Maintenance, Transport, and ServiceStorage Storage, Maintenance, Transport, and Service Transporting the UPS to Another Location Troubleshooting ServiceUPS is not providing expected backup time There is no utility power Radio Frequency Warning Regulatory ApprovalsLimited Warranty Copyright Notice