Configuration Settings
Configuration Settings
Settings are adjusted through PowerChute software, optional SmartSlot accessory cards, or in terminal mode.
Function | Factory | User Selectable | Description | ||
Default | Choices | ||||
|
| ||||
|
|
|
| ||
Automatic | Every 14 days | • Every 7 days | Set the interval at which the UPS will execute a | ||
(336 hours) | (168 hours) |
| |||
|
| • Every 14 days |
| ||
|
| (336 hours) |
|
| |
|
| • On start up only |
| ||
|
| • No |
|
| |
|
|
|
| ||
UPS ID | UPS_IDEN | Up to eight characters | Uniquely identify the UPS, (i.e. server name or | ||
|
| (alphanumeric) | location) for network management purposes. | ||
|
|
|
|
| |
Date of Last | Manufacture | mm/dd/yy |
| Reset this date when you replace the battery | |
Battery | Date |
|
| module. | |
Replacement |
|
|
|
| |
|
|
|
|
| |
Minimum | 0 percent | • 0% | • 60% | Specify the percentage to which batteries will be | |
Capacity Before |
| • 15% | • 75% | charged following a low battery shutdown before | |
Return from |
| • 30% | • 90% | powering connected equipment. | |
Shutdown |
|
| |||
| • 45% |
|
| ||
|
|
|
| ||
|
|
|
|
| |
Alarm Delay | Enable | • Enable | • Disable | Mute ongoing alarms or disable all alarms | |
|
| • Mute |
| permanently. | |
|
|
|
|
| |
Shutdown Delay | 90 seconds | • 0 s | • 360 s | Set the interval between the time when the UPS | |
|
| • 90 s | • 450 s | receives a shutdown command and actual | |
|
| • 180 s | • 540 s | shutdown. | |
|
| • 270 s | • 630 s |
| |
|
|
|
|
| |
Low Battery | 2 minutes | • 2 m | • 14 m | PowerChute software interface provides | |
Warning |
| • 5 m | • 17 m | automatic, unattended shutdown when | |
|
| • 8 m | • 20 m | approximately two minutes of battery operated | |
|
| run time remains. | |||
|
| • 11 m | • 23 m | ||
|
| The | |||
|
|
|
| ||
|
|
|
| when two minutes of run time remain. | |
|
|
|
| Change the low battery warning interval setting to | |
|
|
|
| the time that the operating system or system | |
|
|
|
| software requires to safely shut down. | |
|
|
|
|
| |
Synchronized | 0 seconds | • 0 s | • 240 s | Specify the time the UPS will wait after the return | |
| • 60 s | • 300 s | of utility power before start up (to avoid branch | ||
|
| • 120 s | • 360 s | circuit overload). | |
|
| • 180 s | • 420 s |
| |
|
|
|
|
|
10 |