4.0 Initial Start-up and Phase Check

After installing the unit, use this section to perform the initial start-up and the phase check for the Maintenance Bypass Panel.

4.1Initial Start-up and Phase Check (Internal Batteries)

This section is applicable for INITIAL STARTUP of an APC Silcon BC Series UPS with APC Supplied Maintenance Bypass Panel ONLY.

WARNING

Some units have been programmed at the factory for “autostart”. If programmed for “autostart”, the unit will turn on when utility (AC line) is applied (after a 60-second delay). For more information or to change this feature, see the User Guide.

Before continuing, read the warnings on page 2 of this Installation Guide.

CAUTION!

No load should be connected when this procedure is carried out.

1.Make sure that all AC and DC power is off.

2.Set the UPS bypass switch to “UPS”.

3.Make sure that the main circuit breaker in the load panel is off so that the loads cannot receive power from the UPS.

4.Open the UPS front door(s).

5.Remove the retaining brackets for the fuse holder containing DC fuses F001, F002, and F003. See Component Overview illustration in this Installation Guide for location of fuse holder.

6.At the utility input, switch on the input power to the Maintenance Bypass Panel.

7.At the Maintenance Bypass Panel, set the UPS AC disconnect switch to “ON”. The UPS display should show “System type xxkVA xxxV”.

8.Within 20 seconds, the display should show **Stand-by** and an audible alarm should sound.

9.Check the phase rotation at the service panel and the unit. The unit will not start if the phase rotation is incorrect. The phase rotation must be A, B, C and clockwise.

10.When the audible alarm stops, press the green “ON” button located inside the UPS front door. The display should show “Normal operation load power xx%”.

NOTICE!

One or more alarms may occur. If the alarm(s) persists for more than 20 seconds, refer to the “Alarms” section of the User Guide. If the unit activates a “battery monitor alarm”, you should set the user parameter “battery monitor reset” to “ON”

11.Open DC fuse holder (F001, F002, F003). For location of DC fuse holder, see Component Overview illustration.

12.Place the DC fuses in the fuse holder. Make sure that the red tab on the fuse faces the top of the fuse holder. Make sure that the fuse locking tabs are aligned in the slots on the fuse holder. See DC Fuses illustration.

13.Press each fuse into place. The fuse will “click” into place when it is locked in correctly. 14. Using an open palm, close the fuse holder.

990-1378

34

Installation Guide APC BC300 Series 10kW 208/450/480V UPS

Image 34
Contents APC BC300 Series 10kW 208/450/480V Installation Guide Copyright 2002 APC Denmark ApSSafety Symbols used in this manual Installation Guide APC BC300 Series 10kW 208/450/480V UPSThank You Contents Tools and Equipment Needed IntroductionIntroduction Insulated Tools and Other Equipment NeededReceiving, Unpacking and Moving to Site Please RecycleInstallation InstallationRequirements on Site UPS Footprint measurements in inches & mm Installing the Conduit Connection KitInsulated and other tools required Installing Pedestals Conduit Connection Kit ContentsInstalling Conduit Box and Base Covers Installing the Maintenance Bypass Panel and UPS SBP Electrical Schematic 208V SBP Electrical Schematic SBP Electromechanical 10kW 208V SBP Electromechanical 10kW Component Overview door open Component OverviewWire Terminals Wire TerminalsWiring Diagram for BC300 Utility inputSingle Line Diagram for BC300 Single Line Diagram for BC300Wiring Line Diagram for BC300 25A.T UPS Model Input Output Recom DC Voltage DC Current Mended MIBExternal Connection Board External Connection BoardCommunication Interface Board Option Communication Interface BoardSmart Slot and Connection of Triple Chassis Communication InterfaceProduct Description Safety WarningsAPC BC300 Triple Chassis Monitoring PortInstalling Management Cards Power InputInstalling Management Products To UPS PortPower Considerations Cascading setup of the APC BC300 Triple ChassisPowering the APC BC300 Triple Chassis Power AdaptersTroubleshooting Triple Chassis Power ConsiderationsDetermining Power Requirements Problem Possible Cause SolutionProduct Specifications Monitoring Port Pin Assignments Monitoring Port Pin Assignment Battery Installation Installation of External Batteries and Battery BreakerPower, Physical, and Environmental Specifications PhysicalBattery Installation Guidelines Do not connect the negative cables to the UPS yet Battery Replacement Initial Start-up and Phase Check Initial Start-up and Phase CheckInitial Start-up and Phase Check Internal Batteries Initial Start-up and Phase Check External Batteries DC FusesInitial Start-up and Phase Check Clearing the Events Log Clearing the Events LogStart-up and Shutdown Procedure Start-up and Shutdown ProcedureStart-up from Maintenance Bypass Shutdown Procedure If you have shut the loads down Move on to stepTechnical Specifications Technical SpecificationsAPC BC300 Series 10kW Technical Data Battery Specifications GeneralDimensions/Weight BC300 Series UPS 10kWAPC Corporate How to Contact APCHow to Contact APC Fairgrounds Road West Kingston, RIHow to Contact APC

990-1378 specifications

The APC 990-1378 is a high-performance power supply designed for environments where reliability and efficiency are paramount. As a part of APC's range of power protection solutions, this unit is specifically engineered to safeguard critical electronic devices and maintain consistent power delivery even under demanding conditions.

One of the main features of the APC 990-1378 is its robust battery backup system. This ensures that connected devices remain operational during power outages, providing peace of mind for businesses and individuals relying on constant power supply for applications such as networking, telecommunications, and computer systems. The unit is equipped with advanced battery management technology that extends battery life while optimizing energy consumption.

In terms of technologies, the APC 990-1378 incorporates sine wave output, which delivers clean and stable power suitable for sensitive electronic equipment. This feature is essential for preventing equipment damage caused by power surges or fluctuations. Moreover, the power supply comes with multiple outlets, allowing users to connect several devices simultaneously without compromising performance.

Another characteristic that sets the APC 990-1378 apart is its intelligent LCD display. This user-friendly interface provides real-time information on power consumption, battery status, and system health, allowing users to monitor performance easily. The display also features customizable settings, giving users the flexibility to adapt the unit to their specific needs.

The build quality of the APC 990-1378 is impressive, designed to endure both indoor and outdoor environments. Its rugged casing and efficient cooling system guarantee reliable operation in various conditions, making it suitable for different applications, from home offices to enterprise data centers. Additionally, the compact design of this power supply saves valuable space, an essential consideration for users with limited installation areas.

The APC 990-1378 is also compatible with various management software solutions that facilitate remote monitoring and control. This capability is particularly beneficial for IT administrators who need to manage multiple units across different locations efficiently.

In summary, the APC 990-1378 is a versatile and reliable power supply that prioritizes performance, safety, and user convenience. Its advanced features and technologies make it a valuable asset for anyone seeking reliable power protection solutions in today's increasingly tech-driven world.