American Power Conversion 5000 VA user manual User Configurable Items

Page 10

USER CONFIGURABLE ITEMS

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL SMART SLOT ACCESSORY CARDS, OR TERMINAL MODE.

FUNCTION

FACTORY

USER SELECTABLE

DESCRIPTION

DEFAULT

CHOICES

 

 

Automatic Self-Test

On start-up and

On start-up and every 7

Set the interval at which the

 

every 14 days,

days thereafter

UPS will execute a self-test.

 

thereafter

On start-up and every 14

 

 

 

days thereafter

 

 

 

On start-up only

 

 

 

No self-test

 

 

 

 

 

Date of Last Battery

Manufacture date

Date of

Reset this date when you replace

Replacement

 

battery replacement

the battery modules.

 

 

 

 

Minimum Run time

0 seconds

0 to 3600 s of run time

Specify the minimum run time

Before Return from

 

 

following a low battery

Shutdown

 

 

shutdown, before powering

 

 

 

connected equipment.

Audible Alarm

ON

ON, OFF

Enable or disable all alarms

Setting

 

 

permanently.

 

 

 

 

Simple Shutdown

90 seconds

0 to 1800 s

Set the interval between the time

Delay

 

 

when the UPS receives a simple

 

 

 

shutdown command and the

 

 

 

actual shutdown.

 

 

 

 

Simple Low Run

150 seconds

0 to 1800 s

Change the warning interval

Time Warning

 

 

default to a higher setting if the

 

 

 

operating system requires a

 

 

 

longer interval for shutdown.

 

 

 

The low battery warning beeps

 

 

 

are continuous when 150

 

 

 

seconds of run time remain.

 

 

 

 

High Bypass Point

 

Output Voltage Setting

Maximum voltage that the UPS

 

255 VAC

200 VAC:

will pass to connected

 

 

210 - 280 VAC

equipment during internal

 

 

bypass operation.

 

 

208 VAC:

 

 

 

 

 

220 - 280 VAC

 

 

 

220 VAC:

 

 

 

235 - 280 VAC

 

 

 

230 VAC:

 

 

 

245 - 280 VAC

 

 

 

240 VAC:

 

 

 

255 - 280 VAC

 

 

 

 

 

8

Image 10
Contents APC Smart-UPSRT Page Introduction SpecificationsUnpacking Wiring and Connecting the UPS Connecting the Battery Modules and Attaching the Front Bezel Normal bypass Avoid using extension cords Operation Does not affect the voltage display User Configurable Items XLJ models Connecting the EPO Emergency Power OFF Option Terminal Mode to Configure UPS Parameters VA models Page Replacing the Battery Module Disconnecting the Battery for Transport TROUBLESHOOTING, SERVICE, and Warranty Information Bypass LED Illuminates Service Limited WarrantyRegulatory Agency Approvals and Radio Frequency Warnings 200, 208, 220, 230, 240 V ModelsDeclaration of Conformity APC Worldwide Customer Support