USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL SMART SLOT ACCESSORY CARDS, OR TERMINAL MODE.
FUNCTION | FACTORY | USER SELECTABLE | DESCRIPTION | |
DEFAULT | CHOICES | |||
|
| |||
Automatic | On | On | Set the interval at which the | |
| every 14 days, | days thereafter | UPS will execute a | |
| thereafter | On |
| |
|
| days thereafter |
| |
|
| On |
| |
|
| No |
| |
|
|
|
| |
Date of Last Battery | Manufacture date | Date of | Reset this date when you replace | |
Replacement |
| battery replacement | the battery modules. | |
|
|
|
| |
Minimum Run time | 0 seconds | 0 to 3600 s of run time | Specify the minimum run time | |
Before Return from |
|
| following a low battery | |
Shutdown |
|
| shutdown, before powering | |
|
|
| connected equipment. | |
Audible Alarm | ON | ON, OFF | Enable or disable all alarms | |
Setting |
|
| permanently. | |
|
|
|
| |
Simple Shutdown | 90 seconds | 0 to 1800 s | Set the interval between the time | |
Delay |
|
| when the UPS receives a simple | |
|
|
| shutdown command and the | |
|
|
| actual shutdown. | |
|
|
|
| |
Simple Low Run | 150 seconds | 0 to 1800 s | Change the warning interval | |
Time Warning |
|
| default to a higher setting if the | |
|
|
| operating system requires a | |
|
|
| longer interval for shutdown. | |
|
|
| The low battery warning beeps | |
|
|
| are continuous when 150 | |
|
|
| seconds of run time remain. | |
|
|
|
| |
High Bypass Point |
| Output Voltage Setting | Maximum voltage that the UPS | |
| 255 VAC | 200 VAC: | will pass to connected | |
|
| 210 - 280 VAC | equipment during internal | |
|
| bypass operation. | ||
|
| 208 VAC: | ||
|
|
| ||
|
| 220 - 280 VAC |
| |
|
| 220 VAC: |
| |
|
| 235 - 280 VAC |
| |
|
| 230 VAC: |
| |
|
| 245 - 280 VAC |
| |
|
| 240 VAC: |
| |
|
| 255 - 280 VAC |
| |
|
|
|
|
8