Troubleshooting

Troubleshooting

Use this table to solve minor UPS installation and operation problems. Refer to www.apc.com for assistance with complex UPS problems.

Problem and/or Possible Cause

Solution

 

 

UPS will not turn on

 

 

 

The battery is not connected properly.

Check that the battery connector is fully engaged.

 

 

Test button not pushed.

Press the Test button once to power-up the UPS and connected equipment.

 

 

The UPS is not connected to utility

Check that the power cable from the UPS to the utility power supply is

power supply.

securely connected at both ends.

 

 

Very low or no utility voltage.

Check the utility power supply to the UPS by plugging in a table lamp. If the

 

light is very dim, have the utility voltage checked.

 

 

UPS will not turn off

 

 

 

The UPS is experiencing an internal

Do not attempt to use the UPS. Unplug the UPS and have it serviced

fault.

immediately.

 

 

UPS beeps occasionally

 

 

 

Normal UPS operation when running

None: The UPS is protecting the connected equipment.

on battery.

Press the Test button to silence this alarm.

 

 

UPS is not providing expected backup time

 

 

The UPS battery(s) are weak due to a

Charge the battery(s). Batteries require recharging after extended outages.

recent power outage or battery(s) are

Batteries can wear faster when put into service often or when operated at

near the end of their service life.

elevated temperatures. If the battery(s) are near the end of their service life,

 

consider replacing the battery(s) even if the Replace Battery LED is not yet

 

illuminated.

 

 

All LEDs are illuminated and the UPS emits a constant beeping

 

 

The UPS is experiencing an internal

Do not attempt to use the UPS. Unplug the UPS and have it serviced

fault.

immediately.

 

 

Front panel LEDs flash sequentially

 

 

 

The UPS has been shut down remotely

None: The UPS will restart automatically when utility power returns.

through software or an optional

 

accessory card.

 

 

 

All LEDs are off and the UPS is plugged into a wall outlet

 

 

The UPS is shut down or the battery is

None: The UPS will restart automatically when utility power is restored and

discharged from an extended outage.

the battery has a sufficient charge.

 

 

16

Smart-UPS XL 3U Rack Mount 2200/3000 VA 120/230 Vac; 3000 VA 100/200 Vac User Manual

Image 16
Contents Smart-UPSXL Page Accessories Read the Safety Guide before installing the UPSIntroduction About this UPSSpecifications Install the Rails in the Rack InstallationInstall the UPS in the Rack and Connect the Battery Module Rear Panel Features Rear PanelsStart-up and Operation Start the UPSIndicator Indicator Title Description Display Panel Indicators and Function ButtonsDisplay Panels Feature Feature Title Function Button Configuration UPS settingsFunction Factory User Selectable Description Default Choices Connect the Emergency Power Off option Configure UPS parameters User Name apc Password apcPress 3 and Enter to select Configuration Press 2 and Enter to change Battery SettingsMaintenance, Transport, and Service Replacing the Battery ModuleTroubleshooting Problem and/or Possible Cause SolutionProblem and/or Possible Cause Solution There is no utility power Regulatory and Warranty Information Regulatory Agency Approvals and Radio Frequency WarningsFCC Compliance Notice Models 100/200 V modelsTwo-YearLimited Warranty Terms of warrantyDate of product declaration APC Worldwide Customer Support