APC SUA2200/3000 VA 120/230 VAC manual Configuration, UPS settings

Page 10

Configuration

Configuration

UPS settings

Settings are adjusted through PowerChute software or optional SmartSlot accessory cards.

Function

Factory

User Selectable

Description

Default

Choices

 

 

 

 

Automatic

On startup and

• Every 7 days

Set the interval at which the UPS will execute a

Self-Test

every 14 days

(168 hours)

 

self-test.

 

(336 hours)

• On startup and every

 

 

there after

14 days (336 hours)

 

 

 

there after

 

 

 

 

• On startup only

 

 

 

• No self-test

 

 

 

 

 

 

UPS ID

UPS_IDEN

Up to eight characters

Uniquely identify the UPS, (i.e. server name or

 

 

(alphanumeric)

location) for network management purposes.

 

 

 

 

 

Date of Last

Manufacture

mm/dd/yy

 

Reset this date when you replace the battery

Battery

Date

 

 

module.

Replacement

 

 

 

 

 

 

 

 

 

Minimum Capacity

0 percent

• 0%

• 60%

Specify the percentage to which batteries will

Before Return from

 

• 15%

• 75%

be charged following a low battery shutdown

Shutdown

 

• 30%

• 90%

before powering connected equipment.

 

 

• 45%

 

 

 

 

 

 

 

Voltage Sensitivity

High sensitivity

Brightly

 

Adjust by pressing the Sensitivity switch

The UPS detects

 

illuminated: high

located on the rear panel next to the green

 

sensitivity

Sensitivity LED. Use a pointed object, such as

and reacts to line

 

 

 

 

a pen to do so.

voltage distortions

 

Dimly illuminated:

by transferring to

 

medium sensitivity

Note: In situations of poor power quality, the

battery operation to

 

No illumination:

UPS may frequently transfer to battery

protect the

 

operation. If the connected equipment can

 

low sensitivity

connected

 

operate normally under such conditions, reduce

 

 

 

equipment.

 

 

 

the sensitivity setting to conserve battery

 

 

 

 

capacity and service life.

 

 

 

 

Voltage sensitivity levels can be changed

 

 

 

 

through PowerChute software.

 

 

 

 

 

Alarm Delay

Enable

• Enable

 

Mute ongoing alarms or disable all alarms

Control

 

• Mute

 

permanently.

 

 

• Disable

 

 

 

 

 

 

 

Shutdown Delay

90 seconds

• 0 s

• 360 s

Set the interval between the time when the UPS

 

 

• 90 s

• 450 s

receives a shutdown command and actual

 

 

• 180 s

• 540 s

shutdown.

 

 

• 270 s

• 630 s

 

 

 

 

 

 

10

Smart-UPS XL 3U Rack Mount 2200/3000 VA 120/230 Vac; 3000 VA 100/200 Vac User Manual

Image 10
Contents Smart-UPSXL Page Introduction AccessoriesRead the Safety Guide before installing the UPS About this UPSSpecifications Install the Rails in the Rack InstallationInstall the UPS in the Rack and Connect the Battery Module Rear Panel Features Rear PanelsStart-up and Operation Start the UPSIndicator Indicator Title Description Display Panel Indicators and Function ButtonsDisplay Panels Feature Feature Title Function Button Configuration UPS settingsFunction Factory User Selectable Description Default Choices Connect the Emergency Power Off option Configure UPS parameters User Name apc Password apcPress 3 and Enter to select Configuration Press 2 and Enter to change Battery SettingsMaintenance, Transport, and Service Replacing the Battery ModuleTroubleshooting Problem and/or Possible Cause SolutionProblem and/or Possible Cause Solution There is no utility power FCC Compliance Notice Models Regulatory and Warranty InformationRegulatory Agency Approvals and Radio Frequency Warnings 100/200 V modelsTwo-YearLimited Warranty Terms of warrantyDate of product declaration APC Worldwide Customer Support