
Troubleshooting
Problem and Possible Cause  | Solution  | 
The UPS will not turn on or there is no output.
The UPS has not been turned on.  | Press the ON button once to turn on the UPS.  | 
  | 
  | 
The UPS is not connected to AC power.  | Be sure the power cable is securely connected to the UPS and to the AC power  | 
  | supply.  | 
  | 
  | 
The input circuit breaker has tripped.  | Disconnect nonessential equipment and reset the circuit breaker.  | 
  | 
  | 
The UPS shows very low or no AC input  | Check the AC power supply to the UPS by plugging in a table lamp. If the light is  | 
voltage.  | very dim, check the AC voltage.  | 
  | 
  | 
The battery is not securely connected.  | Be sure that all battery connections are secure.  | 
  | 
  | 
There is an internal UPS fault.  | Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.  | 
The UPS is operating on battery while connected to input AC power.
The input circuit breaker has tripped.  | Disconnect nonessential equipment and reset the circuit breaker.  | 
  | 
  | 
There is very high, very low, or distorted input  | Move the UPS to a different outlet on a different circuit. Test the input voltage with  | 
line voltage.  | the AC voltage display. If acceptable to the connected equipment, reduce the UPS  | 
  | sensitivity.  | 
The UPS is emitting an audible beeping sound.
The UPS is operating normally.  | None. The UPS is protecting the connected equipment.  | 
The UPS does not provide expected battery backup time.
The UPS battery is weak due to a  | Charge the battery. Batteries require recharging after an extended outage.  | 
recent power outage or is near the end  | Elevated ambient temperatures, poor quality AC power, and frequent short duration  | 
of its service life.  | discharges will shorten battery life.  | 
  | If the battery is near the end of its service life, consider replacing the battery even if  | 
  | the replace battery icon is not illuminated.  | 
  | 
  | 
The UPS is experiencing an overload  | Check the UPS load display. Unplug nonessential equipment, such as printers.  | 
condition.  | 
  | 
The Fault LED is illuminated. The UPS displays a fault message and emits a constant beeping sound.
Internal UPS fault.  | Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately.  | 
  | If more than one fault is present the fault messages will be displayed alternately on  | 
  | display screen.  | 
  | 
  | 
The Replace Battery icon is illuminated. | 
  | 
  | 
  | 
The battery has a weak charge.  | Allow the battery to recharge for at least four hours. Then, perform a  | 
  | |
  | 
  | 
The replacement battery is not  | Be sure the battery connector is securely connected.  | 
properly connected.  | 
  | 
  | 
  | 
Site Wiring Fault LED is flashing. | 
  | 
Wiring faults detected include missing ground, 
If the UPS indicates a site wiring fault, have a qualified electrician inspect the building wiring, applicable for 120 Vac units only.
9  |