APC 208 Vac user manual Communication Ports, Emergency Power Off

Page 13

Communication Ports

SERIAL PORT Use only the supplied cable to connect to the serial port. A standard serial interface cable is incompatible with the UPS.

Emergency Power Off

The emergency power off (EPO) feature is user configurable. EPO provides immediate de-energizing of connected equipment from a remote location, without switching to battery operation.

1.Use the EPO connector supplied with the UPS.

2.Use a normally-open contact to connect the +24 terminal to the IN terminal. External voltage is not required.

3.Wire the four-pin connector to the EPO system.

EPO PORT

(located on rear panel)

EPO

Connector

The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential. Such closure circuits may be provided by a switch or relay properly isolated from the utility. To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a closure type circuit.

Use one of the following cable types to connect the UPS to the EPO switch.

CL2: Class 2 cable for general use.

CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.

CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.

CLEX: Limited use cable for use in dwellings and for use in raceways.

For installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable).

For installation in other countries: Use standard low-voltage cable in accordance with national and local regulations.

Smart-UPS 5000 VA 208/230 Vac Tower/Rack-Mount 5U User Manual

9

For further information contact UPS Direct Ltd:

Tel: 08456 445 002 - Fax: 08456 445 003 - Email: info@upsdirect.com - Website: www.upsdirect.com

Image 13
Contents APC Smart-UPS≤ Page Contents Page About this UPS Read the Safety Guide before installing the UPSUnpack Installation SpecificationsRack-mount configuration Install rack-mount brackets and rail cleatsInstall unit in rack Install stabilizer brackets Rack-mount to tower conversion procedureInstall two top covers Accessories Input hardwire 230 V models onlyConnect the ground wire prior to connecting the line wires Rack-mount configuration Tower configuration Configure bezelConnect batteries Rack-mount configuration Connect display cable and install bezelRear Panels Connect Equipment and Power to the UPSStart the UPS Communication Ports Emergency Power OffIndicator Indicator Title Description Display Panel Indicators and Function ButtonsDisplay Panels ModelsFeature Feature Title Function Button Function Factory User Selectable Description Default Choices UPS settingsBrightly Problem and/or Possible Cause Solution TroubleshootingInput circuit breaker trips Replace Battery/Battery Disconnected LED is illuminatedAVR Boost or AVR Trim LEDs are illuminated UPS operates on battery although line voltage exists There is no utility powerBattery Charge and Load LEDs flash simultaneously Diagnostic utility voltageReplace battery modules Maintenance, Transport, and ServiceInstall new batteries Service Terms of warranty Two-Year WarrantyDate of product declaration