5:STORAGE AND MAINTENANCE

Storage

Store the UPS covered in a cool, dry location, with the battery fully charged.

At -15 to +30 °C (+5 to +86 °F), charge the UPS battery every six months.

At +30 to +45 °C (+86 to +113 °F), charge the UPS battery every three months.

Battery Replacement

The UPS battery life differs based on usage and environment. Consider replacing the battery every three years.

This UPS has an easy to replace, hot-swappable battery. Replacement is a safe procedure, isolated from electri- cal hazards. You may leave the UPS and connected equipment on during the replacement procedure. See your dealer or contact APC (see Contact Information) for information on replacement batteries.

Note: Upon battery disconnection, equipment is not protected from power outages.

For the battery replacement procedure, refer to applicable steps in Mount the UPS in a Rack.

Be sure to deliver the spent battery to a recycling facility or ship it to APC in the replacement battery packing material.

9

Image 11
Contents APC Server and Network UPS Page Position the UPS InstallationIntroduction UnpackTower Configuration Mount the UPS in a Two-Post Rack Reinstall battery, battery bracket, and screws Start UP Connect Equipment to the UPSConnect the UPS to the Network if Applicable Start the UPS Operation Front Display PanelUPS ID Upsiden User Configurable ItemsFunction Factory User Selectable Description Default Choices Storage Battery ReplacementStorage and Maintenance TROUBLESHOOTING, SHIPPING, and Service Replace BATTERY/BATTERY Disconnected LED is Illuminated Shipping and Service Regulatory Information Regulatory and Warranty Information