American Power Conversion 1000 VA Function Factory User Selectable Description Default Choices

Page 10

NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE

 

FUNCTION

 

 

FACTORY

 

 

USER SELECTABLE

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

DEFAULT

 

 

CHOICES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Battery

 

2 minutes

 

2, 5, 7, 10 minutes

 

The UPS will beep when 2 minutes of

 

Warning

 

PowerChute

 

(Times are approxi-

 

battery runtime remains.

 

 

 

 

 

 

 

 

 

 

 

 

Business Edition

 

mate.)

 

Change the low battery warning inter-

 

 

 

 

software provides

 

 

 

 

val setting to the time that the operat-

 

 

 

 

automatic, unat-

 

 

 

 

ing system or system software requires

 

 

 

 

tended shutdown

 

 

 

 

to safely shut down.

 

 

 

 

when approxi-

 

 

 

 

 

 

 

 

 

 

mately 2 minutes

 

 

 

 

 

 

 

 

 

 

of battery oper-

 

 

 

 

 

 

 

 

 

 

ated runtime re-

 

 

 

 

 

 

 

 

 

 

mains.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Synchronized

 

0 seconds

 

0, 15, 45, 75 seconds

 

Specify the time the UPS will wait

 

Turn-on Delay

 

 

 

 

 

 

 

after the return of utility power before

 

 

 

 

 

 

 

 

 

 

turn-on (to avoid branch circuit over-

 

 

 

 

 

 

 

 

 

 

load).

 

 

 

 

 

 

 

 

 

High Transfer

 

127 Vac

127, 130, 133, 136

 

 

Set the high transfer point higher to

 

Point

 

 

 

 

Vac

 

avoid unnecessary battery usage when

 

 

 

 

 

 

 

 

 

 

the utility voltage is usually high and

 

 

 

 

 

 

 

 

 

 

the connected equipment is specified

 

 

 

 

 

 

 

 

 

 

to operate with input voltages this

 

 

 

 

 

 

 

 

 

 

high.

 

 

 

 

 

 

 

 

 

Low Transfer Point

 

106 Vac

97, 100, 103, 106

 

 

Set the low transfer point lower when

 

 

 

 

 

 

 

Vac

 

the utility voltage is usually low and

 

 

 

 

 

 

 

 

 

 

the connected equipment is specified

 

 

 

 

 

 

 

 

 

 

to operate with input voltages this low.

 

 

 

 

 

 

 

 

 

 

 

 

8

Image 10
Contents APC Server and Network UPS Page Unpack InstallationIntroduction Position the UPSTower Configuration Mount the UPS in a Two-Post Rack Reinstall battery, battery bracket, and screws Connect the UPS to the Network if Applicable Connect Equipment to the UPSStart UP Start the UPS Front Display Panel OperationUser Configurable Items UPS ID UpsidenFunction Factory User Selectable Description Default Choices Storage and Maintenance Battery ReplacementStorage TROUBLESHOOTING, SHIPPING, and Service Replace BATTERY/BATTERY Disconnected LED is Illuminated Shipping and Service Regulatory and Warranty Information Regulatory Information