American Power Conversion 1000 VA user manual TROUBLESHOOTING, SHIPPING, and Service

Page 12

6:TROUBLESHOOTING, SHIPPING, AND SERVICE

Use the chart below to solve minor UPS installation and operation problems. Refer to www.apc.com with complex UPS problems.

PROBLEM AND/OR POSSIBLE

SOLUTION

CAUSE

 

UPS WILL NOT TURN ON

 

 

 

UPS not connected to utility

Check that the power cord from the UPS to the utility power supply is se-

power supply.

curely connected.

 

 

Battery not connected prop-

Ensure that the battery is properly connected.

erly.

 

 

 

Very low or no utility voltage.

Check the utility power supply to the UPS by plugging in a table lamp. If the

 

light is very dim, have the utility voltage checked.

 

 

UPS WILL NOT TURN OFF

 

 

 

Internal UPS fault.

Do not attempt to use the UPS. Unplug the UPS, disconnect the battery, and

 

have it serviced immediately.

 

 

UPS BEEPS OCCASIONALLY

 

Normal operating UPS beeps

None. The UPS is protecting the connected equipment from occasional util-

when running on battery.

ity power irregularities.

 

 

UPS IS NOT PROVIDING EXPECTED BACKUP TIME

 

 

The UPS battery is weak due

Charge the battery. Batteries require recharging after extended outages, and

to a recent outage or is near

wear faster when frequently put into service or when operated at elevated

the end of the service life.

temperatures. If the battery is near the end of the service life, consider re-

 

placing even if the replace battery LED is not yet illuminated.

 

 

ON-LINE AND OVERLOAD LEDS ARE FLASHING ALTERNATELY

The UPS was shut down

None. The UPS will restart when utility power returns.

through PowerChute.

 

 

 

ON-LINE AND ON-BATTERY LEDS ARE FLASHING, OR, OVERLOAD LED IS FLASHING

 

 

Internal UPS fault. The UPS

Do not attempt to use the UPS. Turn off the UPS, unplug the battery, and

has shut down.

have it serviced immediately.

 

 

ALL LEDS ARE OFF AND THE UPS IS PLUGGED INTO A WALL OUTLET

 

 

The UPS is shut down or the

None. The UPS will return to normal operation when the power is restored

battery is discharged from an

and the battery has a sufficient charge.

extended outage.

 

 

 

10

Image 12
Contents APC Server and Network UPS Page Installation IntroductionUnpack Position the UPSTower Configuration Mount the UPS in a Two-Post Rack Reinstall battery, battery bracket, and screws Connect Equipment to the UPS Connect the UPS to the Network if ApplicableStart UP Start the UPS Front Display Panel OperationUser Configurable Items UPS ID UpsidenFunction Factory User Selectable Description Default Choices Battery Replacement Storage and MaintenanceStorage TROUBLESHOOTING, SHIPPING, and Service Replace BATTERY/BATTERY Disconnected LED is Illuminated Shipping and Service Regulatory and Warranty Information Regulatory Information