APC 1400XLT, 3000T, 5000T, 2200XLT user manual Battery Replacement Procedure 3U Rack Mount Units

Page 19

Battery Replacement Procedure - 3U Rack Mount Units

1.Reach into the finger pull and open the front cover. Swing the cover open as shown.

2.Unhook the side of the cover from the chassis and lift it away to expose the battery door.

3.Use a flat-blade or Phillips screwdriver or a coin to remove the two battery door screws and open the door.

4.Grasp the tab and gently pull the battery out of the UPS.

5.Disconnect the battery leads. Loosen the connectors by gently wiggling them while pulling straight back from the battery connector.

6.Connect the battery leads to the new battery. Connect the red wire to the positive (+) terminal and the black wire to the negative (–) terminal.

7.Slide the battery into the UPS.

8.Close the battery door, replace the battery compartment screws, and replace the front cover.

Notes:

Be careful removing the batteries - they are heavy.

Small sparks at the battery connectors are normal during connection.

Batteries must be recycled. Deliver the battery to an appropriate recycling facility or ship it to the supplier in the new battery’s packing material. See the new battery instructions for more information.

13

990-7031D, Revision 5 5/01

Image 19
Contents 990-7031D, Revision 5 5/01 990-7031D, Revision 5 5/01 Electrical Safety Handling SafetyReplacement and Recycling of Batteries 990-7031D, Revision 5 5/01 Table of Contents Page Introduction InstallationUnpacking Installing Rack Mount Units PlacementFront Rack Mount Options Load the UPS into the RackTower Units Connect the Batteries5U Rack Mount Units 3U Rack Mount UnitsInitial Startup Charge the batteryRear Views Operating Instructions Replace Battery On BatteryBattery Charge Bar Graph Shutdown ModeCold start is not a normal condition Low BatterySmartBoost Cold StartExtended storage Replacing the BatteryStorage Storage ConditionsBattery Replacement Procedure Tower Units Battery Replacement Procedure 3U Rack Mount Units Battery Replacement Procedure 5U Rack Mount Units 990-7031D, Revision 5 5/01 Tower and 5U Models 1400VA and 2200VA Models User Configuration ItemsHow to Determine On-Battery Run Time Typical On-Battery Runtime Versus Load, in Hours2200 3U Rack Mount Models 2200 & 3000 VA Models Tower and 5U Rack Mount Models 3000 & 5000 VA Models1400 VA 2200 VA 3000 VA 5000 VA SpecificationsTroubleshooting APC Contact Information ServiceLimited Warranty If the UPS requires service do not return it to the dealer990-7031D, Revision 5 5/01 Smart-UPS Battery Protocol XL InstallationClick on Configuration Click on UPS Operating Parameters Use the Smart-UPS Battery Pack Utility BattpackStep Number Type Produced Effect Rack Type Hole Type Hardware Required Hardware Included RacksAppendix C Transporting Your Smart-UPS
Related manuals
Manual 40 pages 63.83 Kb

3000T, 1400XLT, 5000T, 2200XLT specifications

The APC (American Power Conversion) range of Uninterruptible Power Supplies (UPS) includes models such as the 2200XLT, 5000T, 1400XLT, and 3000T, each designed to meet different power protection needs in various environments. These models provide reliable backup power and surge protection, ensuring that electronic devices remain operational during utility power disruptions.

The APC 2200XLT is known for its robust performance and efficiency. This model features on-line double conversion technology, which guarantees that connected equipment receives pure sine wave power, crucial for sensitive electronics. With a power capacity of 2200 VA, the 2200XLT accommodates high-energy requirements, making it ideal for small to medium-sized businesses. The LCD display provides real-time status on power conditions, battery health, and load levels, ensuring users are always informed.

The APC 5000T, with a power capacity of 5000 VA, is designed for larger operations, providing substantial backup power for critical infrastructure. This model offers advanced features such as hot-swappable batteries, allowing maintenance without disrupting power to connected devices. The 5000T also includes PowerChute software, facilitating monitoring and management of UPS systems via a user-friendly interface. Its enhanced scalability means it can easily be expanded to meet growing power needs.

The APC 1400XLT is compact yet efficient, offering 1400 VA of power. It excels in providing reliable protection for desktop computers and workstations. Featuring Power Factor Correction (PFC), this model optimizes power delivery, resulting in increased energy savings. Its customizable alarm settings and easy-to-read LCD panel make it user-friendly, ensuring that even those with minimal technical expertise can operate it effectively.

Lastly, the APC 3000T serves as a versatile powerhouse for small to medium-sized data centers. Its 3000 VA capacity supports critical equipment, while redundant features enhance reliability. The unit is also equipped with a network management card for remote monitoring capabilities. The 3000T's ability to configure and manage multiple units in a parallel setup allows businesses to ensure that their power needs are met while maximizing uptime.

In summary, the APC 2200XLT, 5000T, 1400XLT, and 3000T UPS models offer a variety of features and technologies designed to ensure power availability and system reliability across various applications. These units emphasize security against power disturbances while providing a solid return on investment for organizations seeking to protect their critical electronic infrastructure.