APC 5000T, 3000T, 2200XLT, 1400XLT user manual Specifications, 1400 VA 2200 VA 3000 VA 5000 VA

Page 25

Specifications

 

1400 VA

 

2200 VA

 

 

3000 VA

 

5000 VA

Acceptable input voltage

 

 

0 - 325 VAC

 

Input voltage (on-line operation)*

 

160 - 253

VAC

 

208 volt output range*

 

 

177 - 229 VAC

 

120 volt output range *

 

 

 

 

 

 

 

 

with 400 VA load

 

 

95 - 130 VAC

 

with no load

 

 

100 - 135 VAC

 

Nominal input frequency

 

 

50 or 60 Hz, autosensing

 

Input protection

 

 

Resettable circuit breaker

 

Frequency limits (on-line operation)

 

 

47 to 63 Hz

 

Transfer time

 

 

2 ms typical, 4.5 ms maximum

 

Maximum load, total

1400 VA/950 W

 

2200 VA/1600 W

3000 VA/2250 W

 

5000 VA/3750 W

Maximum load, 120V auxiliary

 

 

400 VA/400 W

 

On-battery output voltage

 

 

208 VAC

 

On-battery frequency

 

 

50 or 60 Hz, ñ0.1 Hz;

 

 

 

unless synchronized to utility during brownout

On-battery waveshape

 

 

Low-distortion sine wave

 

Overload protection (on-battery)

Overcurrent and short -circuit protected, latching shutdown on overload

Overload protection (on-line)

 

2 pole, 20 Amp UL certified input circuit breaker

Overload protection

 

Transformer and output protected by resettable

(120 VAC auxiliary)

 

thermal circuit breaker (on-line and on-battery)

Surge energy rating

 

 

 

 

 

 

 

 

(one time, 10/1000 æs waveform)

 

 

1120 J

 

Surge current capability

 

 

 

 

 

 

 

 

(one time, 8/20 æs waveform)

 

 

6500 A maximum

 

Surge response time

 

 

0 ns (instantaneous) normal mode;

 

 

 

 

<5 ns common mode

 

Surge voltage let -through

 

 

 

 

 

 

 

 

(percentage of applied ANSI C62.41 Cat. A

 

0.30%

 

 

ñ6 kV test waveform)

 

 

 

 

 

 

 

 

Noise filter

 

Normal and common mode EMI/RFI suppression,

 

 

 

100 kHz to 10 MHz

 

Battery type

 

Spill proof, maintenance free, sealed lead-acid

Typical battery life

3 to 6 years, depending on number of discharge cycles

 

 

 

and ambient temperature

 

Typical recharge time

 

 

2 to 5 hours from total discharge

 

Operating temperature

 

 

0 to 40§C (+32 to +104§F)

 

Storage temperature

 

 

-15 to +45§C (+5 to +113§F)

 

Operating and storage relative humidity

 

 

5 to 95%, non-condensing

 

Operating elevation

 

 

0 to +3,000 m (0 to +10,000 ft.)

 

Storage elevation

 

 

0 to +15,000 m (0 to +50,000 ft.)

 

Electromagnetic immunity

 

IEC 801-2 level IV, 801-3 level III, 801-4 level IV

Audible noise in dBA at 1 m (3 ft.)

 

<55

 

 

 

Safety approvals

 

 

Listed to UL 1778, certified to CSA 107.1

 

EMI verification

 

 

FCC/DOC Class A verified

 

 

 

 

5U Units

 

 

RM Units

Size (W x H x D)

 

43.2 x 19.6 x 54.6 cm

 

 

43.2 x 19.6 x 62.2 cm

 

 

(17.0 x 8.7 x 21.5 in.)

 

 

(17.0 x 8.7 x 24.5 in.)

Weight - net (shipping)

120 (143) lb.

 

137 (160) lb.

 

137 (160) lb.

 

225 (245) lb.

 

54.3 (64.8) kg

 

62.0 (72.5) kg

 

62.0 (72.5) kg

 

102 (111) kg

 

 

 

3U Units

 

 

Tower Units

Size (W x H x D)

 

43.2 x 13.3 x 62.2 cm

 

 

19.6 x 43.2 x 62.2 cm

 

 

(17.0 x 5.25 x 24.5 in.)

 

 

(8.7 x 17.5 x 26.0 in.)

Weight - net (shipping)

 

 

128 (148) lb.

 

 

230 (250) lb.

 

 

 

58 (67) kg

 

 

105 (114) kg

19

990-7031D, Revision 5 5/01

Image 25
Contents 990-7031D, Revision 5 5/01 990-7031D, Revision 5 5/01 Electrical Safety Handling SafetyReplacement and Recycling of Batteries 990-7031D, Revision 5 5/01 Table of Contents Page Introduction InstallationUnpacking Installing Rack Mount Units PlacementFront Rack Mount Options Load the UPS into the RackTower Units Connect the Batteries5U Rack Mount Units 3U Rack Mount UnitsInitial Startup Charge the batteryRear Views Operating Instructions Battery Charge Bar Graph On BatteryShutdown Mode Replace BatterySmartBoost Low BatteryCold Start Cold start is not a normal conditionStorage Replacing the BatteryStorage Conditions Extended storageBattery Replacement Procedure Tower Units Battery Replacement Procedure 3U Rack Mount Units Battery Replacement Procedure 5U Rack Mount Units 990-7031D, Revision 5 5/01 How to Determine On-Battery Run Time User Configuration ItemsTypical On-Battery Runtime Versus Load, in Hours Tower and 5U Models 1400VA and 2200VA Models2200 3U Rack Mount Models 2200 & 3000 VA Models Tower and 5U Rack Mount Models 3000 & 5000 VA Models1400 VA 2200 VA 3000 VA 5000 VA SpecificationsTroubleshooting Limited Warranty ServiceIf the UPS requires service do not return it to the dealer APC Contact Information990-7031D, Revision 5 5/01 Smart-UPS Battery Protocol XL InstallationClick on Configuration Click on UPS Operating Parameters Use the Smart-UPS Battery Pack Utility BattpackStep Number Type Produced Effect Rack Type Hole Type Hardware Required Hardware Included RacksAppendix C Transporting Your Smart-UPS
Related manuals
Manual 40 pages 63.83 Kb

3000T, 1400XLT, 5000T, 2200XLT specifications

The APC (American Power Conversion) range of Uninterruptible Power Supplies (UPS) includes models such as the 2200XLT, 5000T, 1400XLT, and 3000T, each designed to meet different power protection needs in various environments. These models provide reliable backup power and surge protection, ensuring that electronic devices remain operational during utility power disruptions.

The APC 2200XLT is known for its robust performance and efficiency. This model features on-line double conversion technology, which guarantees that connected equipment receives pure sine wave power, crucial for sensitive electronics. With a power capacity of 2200 VA, the 2200XLT accommodates high-energy requirements, making it ideal for small to medium-sized businesses. The LCD display provides real-time status on power conditions, battery health, and load levels, ensuring users are always informed.

The APC 5000T, with a power capacity of 5000 VA, is designed for larger operations, providing substantial backup power for critical infrastructure. This model offers advanced features such as hot-swappable batteries, allowing maintenance without disrupting power to connected devices. The 5000T also includes PowerChute software, facilitating monitoring and management of UPS systems via a user-friendly interface. Its enhanced scalability means it can easily be expanded to meet growing power needs.

The APC 1400XLT is compact yet efficient, offering 1400 VA of power. It excels in providing reliable protection for desktop computers and workstations. Featuring Power Factor Correction (PFC), this model optimizes power delivery, resulting in increased energy savings. Its customizable alarm settings and easy-to-read LCD panel make it user-friendly, ensuring that even those with minimal technical expertise can operate it effectively.

Lastly, the APC 3000T serves as a versatile powerhouse for small to medium-sized data centers. Its 3000 VA capacity supports critical equipment, while redundant features enhance reliability. The unit is also equipped with a network management card for remote monitoring capabilities. The 3000T's ability to configure and manage multiple units in a parallel setup allows businesses to ensure that their power needs are met while maximizing uptime.

In summary, the APC 2200XLT, 5000T, 1400XLT, and 3000T UPS models offer a variety of features and technologies designed to ensure power availability and system reliability across various applications. These units emphasize security against power disturbances while providing a solid return on investment for organizations seeking to protect their critical electronic infrastructure.