APC 60-80KW 208/480V UPS manual Yes

Page 11

Stop/Start UPS and Operating the External Service Bypass

Action

1.Set the input switch (Q001) to position 1

2.Wait 5 sec. Open the front door of the UPS and press the green ON key

3.Press on the keyboard

4.

Press

or

on the keyboard until

5.

Press

on the keyboard

6.Press on the keyboard

7.Check light indication on the bypass panel

8.Set the output switch (Q002) to position 1

9.Set the bypass switch (Q003) to position 0

10.Press on the keyboard

11.Press or on the keyboard until

12. Press

on the keyboard

13.Press on the keyboard

14.Press on the keyboard

15. Press

on the keyboard

Display shows

**System OFF**

Normal operation

load power 0%

Bypass operation

: NO

Bypass operation

: YES

Lamp indication on Bypass Panel

Green light (H002) above the output switch handle (Q002) lights up

Green light (H003) above the bypass switch handle (Q003) lights up

Only the light (H003) above the bypass switch handle (Q003) is now on

Display shows

Bypass operation

: YES

Bypass operation

: NO

Normal operation

load power 0%

All lights on the bypass panel switched off

NOTICE!

If battery has been disconnected, please refer to section 2.4.1 UPS start-up.

 

990-4035

 

 

User Guide APC Silcon 60-80kW 208V/480V UPS

11

Image 11
Contents Copyright 2000 APC Denmark ApS APC Silcon 60-80kW 208/480V UPS User GuideThank You Safety Symbols used in this manualUser Guide APC Silcon 60-80kW 208V/480V UPS Contents Display Unit IntroductionIntroduction Start UPS from stand-by Stop/Start UPS and Operating the External Service BypassStop UPS for stand-by Switching off the UPS Stop UPS for complete power downUPS start-up Start UPS from complete power downSystem start-up now completed Bypassing the Single System UPS Operating the External Service Bypass Switch single systemsUPS YES Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Keyboard OperationOperation Batt. load Batt. tank Display of Measured ValuesEconomy Mode Using the Remote DisplayParameter Settings Parameter SettingsParameter Settings Programming Example Switching to Bypass OperationProgramming Keys Load power xx% Mode Comments Alarms and EventsAlarms and Events Displaying the Alarm StackAlarms Description Action Possible AlarmsUnlock Rectifying Alarm Messages Correction of false alarm situations during service Parallel Operation AlarmsBattery Capacity Test Maintenance & TestingMaintenance & Testing Battery Monitoring TestUntil APC Silcon UPS Limited Factory Warranty WarrantyWarranty APC Denmark How to Contact APCHow to Contact APC APC CorporateUser Guide APC Silcon 60-80kW 208V/480V UPS User Guide APC Silcon 60-80kW 208V/480V UPS

60-80KW 208/480V UPS specifications

The APC 60-80KW 208/480V Uninterruptible Power Supply (UPS) is a robust solution designed to ensure continuous power and protection for mission-critical systems and sensitive equipment in data centers and industrial environments. With its impressive capacity, this UPS provides reliable backup power, ensuring operational continuity by delivering clean and stable power to connected loads, even during power disruptions.

One of the standout features of the APC 60-80KW UPS is its dual input configuration, enabling it to operate on both 208V and 480V systems. This flexibility allows businesses to effortlessly integrate the UPS into their existing electrical infrastructure while maintaining high efficiency. The UPS’s modular design further enhances its adaptability, allowing users to scale power capacity as their business grows or adjusts to changing demands.

The system incorporates advanced technologies to optimize performance and energy efficiency. The use of high-efficiency power conversion techniques results in reduced energy consumption and lower operating costs, making this UPS an environmentally friendly choice. Additionally, it features a high power factor, which allows it to deliver more usable power to the load, reducing the total cost of ownership.

The APC 60-80KW UPS also includes an intelligent battery management system that maximizes battery life by monitoring and adjusting charging cycles. It employs a hot-swappable battery design, enabling maintenance and replacements without interrupting power to critical systems. This ensures that organizations can maintain uptime while managing their UPS effectively.

The UPS is equipped with an advanced monitoring system that provides real-time visibility into power conditions and UPS performance. An intuitive graphical display allows users to easily track key metrics, while remote management capabilities ensure that the UPS can be monitored and controlled from anywhere, enhancing operational efficiency.

Safety features are paramount in the design of the APC 60-80KW UPS. It includes robust short-circuit protection and thermal management to prevent overheating and damage. Furthermore, the unit is compliant with various industry standards, ensuring reliable operation in a variety of environments.

In conclusion, the APC 60-80KW 208/480V UPS is a reliable, efficient, and advanced solution designed to safeguard crucial infrastructure against power interruptions. Its features, including modularity, dual input configurations, and intelligent monitoring, make it an ideal choice for organizations seeking to enhance their power reliability and operational effectiveness.