APC 60-80KW 208/480V UPS manual System start-up now completed

Page 8

Stop/Start UPS and Operating the External Service Bypass

1.Check that the system has been in a stable environment for at least 12 hours enabling any condensation to evaporate prior to start-up.

2.Open front door(s)

3.Switch on utility power by closing Q001

If dual utility close bypass input switch Q010 See notice below.

Display shows

System type XXX

XXX kVA - XXX

4. Wait for approx. 10 seconds

5.

Press

on the keyboard

6.

Press

on the keyboard

7.Wait for approx. 1 second

8.Wait for approx. 1 minute

9.Close MCCBs in Battery Breaker Box or Battery Cabinet

10.Press the green ON button

11.Close the front door(s)

Stop charge DC capacitors : YES

Start charge DC capacitors : YES

Data stored

Start charge DC capacitors : YES

Insert fuse or close MCCB

**System OFF**

Normal operation load power XX%

System start-up now completed.

NOTICE!

One of the following display messages will appear by UPS start-up:

“STD”: Standard (single system)

“PAR”: Parallel System

“ECO”: Economy mode (single or parallel systems) (Last message has priority over the other two)

kVA size (XXX) and the voltage reads:

• XXXkVA - 208 (220 or 480 Volt)

990-4035

8

User Guide APC Silcon 60-80kW 208V/480V UPS

Image 8
Contents APC Silcon 60-80kW 208/480V UPS User Guide Copyright 2000 APC Denmark ApSThank You Safety Symbols used in this manualUser Guide APC Silcon 60-80kW 208V/480V UPS Contents Display Unit IntroductionIntroduction Start UPS from stand-by Stop/Start UPS and Operating the External Service BypassStop UPS for stand-by Stop UPS for complete power down Switching off the UPSStart UPS from complete power down UPS start-upSystem start-up now completed Operating the External Service Bypass Switch single systems Bypassing the Single System UPSUPS YES Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Keyboard OperationOperation Display of Measured Values Batt. load Batt. tankUsing the Remote Display Economy ModeParameter Settings Parameter SettingsParameter Settings Programming Example Switching to Bypass OperationProgramming Keys Load power xx% Alarms and Events Alarms and EventsDisplaying the Alarm Stack Mode CommentsPossible Alarms Alarms Description ActionUnlock Rectifying Alarm Messages Parallel Operation Alarms Correction of false alarm situations during serviceMaintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestUntil APC Silcon UPS Limited Factory Warranty WarrantyWarranty How to Contact APC How to Contact APCAPC Corporate APC DenmarkUser Guide APC Silcon 60-80kW 208V/480V UPS User Guide APC Silcon 60-80kW 208V/480V UPS

60-80KW 208/480V UPS specifications

The APC 60-80KW 208/480V Uninterruptible Power Supply (UPS) is a robust solution designed to ensure continuous power and protection for mission-critical systems and sensitive equipment in data centers and industrial environments. With its impressive capacity, this UPS provides reliable backup power, ensuring operational continuity by delivering clean and stable power to connected loads, even during power disruptions.

One of the standout features of the APC 60-80KW UPS is its dual input configuration, enabling it to operate on both 208V and 480V systems. This flexibility allows businesses to effortlessly integrate the UPS into their existing electrical infrastructure while maintaining high efficiency. The UPS’s modular design further enhances its adaptability, allowing users to scale power capacity as their business grows or adjusts to changing demands.

The system incorporates advanced technologies to optimize performance and energy efficiency. The use of high-efficiency power conversion techniques results in reduced energy consumption and lower operating costs, making this UPS an environmentally friendly choice. Additionally, it features a high power factor, which allows it to deliver more usable power to the load, reducing the total cost of ownership.

The APC 60-80KW UPS also includes an intelligent battery management system that maximizes battery life by monitoring and adjusting charging cycles. It employs a hot-swappable battery design, enabling maintenance and replacements without interrupting power to critical systems. This ensures that organizations can maintain uptime while managing their UPS effectively.

The UPS is equipped with an advanced monitoring system that provides real-time visibility into power conditions and UPS performance. An intuitive graphical display allows users to easily track key metrics, while remote management capabilities ensure that the UPS can be monitored and controlled from anywhere, enhancing operational efficiency.

Safety features are paramount in the design of the APC 60-80KW UPS. It includes robust short-circuit protection and thermal management to prevent overheating and damage. Furthermore, the unit is compliant with various industry standards, ensuring reliable operation in a variety of environments.

In conclusion, the APC 60-80KW 208/480V UPS is a reliable, efficient, and advanced solution designed to safeguard crucial infrastructure against power interruptions. Its features, including modularity, dual input configurations, and intelligent monitoring, make it an ideal choice for organizations seeking to enhance their power reliability and operational effectiveness.