APC 60-80KW 208/480V UPS manual Rectifying Alarm Messages

Page 27

 

 

 

Alarms and Events

 

 

 

 

 

 

 

 

 

 

 

40.

RAM1 memory write error

UPS fault

Call for assistance

 

 

 

 

 

 

41.

Memory write error

UPS fault

Call for assistance

 

 

 

 

 

42. Communication to VQ bypass

UPS fault

Call for assistance

 

 

lost

 

 

 

 

 

 

 

43. Communication to VQ output

UPS fault

Call for assistance

 

 

lost

 

 

 

 

 

 

 

 

44.

Communication to DMU lost

UPS fault

Call for assistance

 

 

 

 

 

 

45.

Communication to controller

UPS fault.

Call for assistance

 

 

lost

Display will show invalid UPS

 

 

 

 

data

 

 

 

 

 

 

 

46.

Communication to parallel IF

UPS fault

Call for assistance

 

 

lost

 

 

 

 

 

 

 

 

47.

External shutdown accepted

Remote signal for switching off

 

 

 

UPS accepted.

 

 

 

 

UPS switches off automatically

 

 

 

 

 

 

 

48.

Communication to VQ mains

UPS fault

Call for assistance

 

 

lost

 

 

 

 

 

 

 

 

49.

Bypass syncronization error

The UPS cannot synchronize with

Check if phase rotation of bypass

 

 

 

bypass mains

voltage is correct – if OK, call for

 

 

 

 

assistance

 

 

 

 

 

 

50.

Battery charge error

Transferred to battery operation

Check RFI input fuse and

 

 

 

because of battery charge error

feedback relay

 

 

 

 

 

5.4Rectifying Alarm Messages

Following actions may rectify alarm:

Check local utility supply. Fuses may be blown or supply switched off accidentally

Check if UPS cooling air intake is blocked

Check if load exceeds maximum output capacity

If, with utility power switched on, there is no UPS output voltage - and an attempt to restart the UPS is in vain - use the external service bypass switch to bypass UPS

1.“Battery weak” message appears: Reset “battery weak” signal according to section 4.0 Parameter Settings and initiate battery capacity test according to Section 6.3. Battery Capacity Test. Make a record of obtained back-up time and use battery monitor to reset alarm. Leave the UPS to recharge battery for at least 16 hours. Start up second battery test without changing the load. If the test result shows improved back-up time, continue the test series until no or just insignificant improvements are obtainable. If battery is still weak - call for assistance.

2.“Battery Defective” message appears: Call for assistance. See section 8.0 “How to contact APC”.

990-4035

User Guide APC Silcon 60-80kW 208V/480V UPS

27

Image 27
Contents Copyright 2000 APC Denmark ApS APC Silcon 60-80kW 208/480V UPS User GuideSafety Symbols used in this manual User Guide APC Silcon 60-80kW 208V/480V UPSThank You Contents Introduction IntroductionDisplay Unit Stop/Start UPS and Operating the External Service Bypass Stop UPS for stand-byStart UPS from stand-by Switching off the UPS Stop UPS for complete power downUPS start-up Start UPS from complete power downSystem start-up now completed Bypassing the Single System UPS Operating the External Service Bypass Switch single systemsUPS YES Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Batt. load Batt. tank Display of Measured ValuesEconomy Mode Using the Remote DisplayParameter Settings Parameter SettingsParameter Settings Switching to Bypass Operation Programming KeysProgramming Example Load power xx% Mode Comments Alarms and EventsAlarms and Events Displaying the Alarm StackAlarms Description Action Possible AlarmsUnlock Rectifying Alarm Messages Correction of false alarm situations during service Parallel Operation AlarmsBattery Capacity Test Maintenance & TestingMaintenance & Testing Battery Monitoring TestUntil Warranty WarrantyAPC Silcon UPS Limited Factory Warranty APC Denmark How to Contact APCHow to Contact APC APC CorporateUser Guide APC Silcon 60-80kW 208V/480V UPS User Guide APC Silcon 60-80kW 208V/480V UPS

60-80KW 208/480V UPS specifications

The APC 60-80KW 208/480V Uninterruptible Power Supply (UPS) is a robust solution designed to ensure continuous power and protection for mission-critical systems and sensitive equipment in data centers and industrial environments. With its impressive capacity, this UPS provides reliable backup power, ensuring operational continuity by delivering clean and stable power to connected loads, even during power disruptions.

One of the standout features of the APC 60-80KW UPS is its dual input configuration, enabling it to operate on both 208V and 480V systems. This flexibility allows businesses to effortlessly integrate the UPS into their existing electrical infrastructure while maintaining high efficiency. The UPS’s modular design further enhances its adaptability, allowing users to scale power capacity as their business grows or adjusts to changing demands.

The system incorporates advanced technologies to optimize performance and energy efficiency. The use of high-efficiency power conversion techniques results in reduced energy consumption and lower operating costs, making this UPS an environmentally friendly choice. Additionally, it features a high power factor, which allows it to deliver more usable power to the load, reducing the total cost of ownership.

The APC 60-80KW UPS also includes an intelligent battery management system that maximizes battery life by monitoring and adjusting charging cycles. It employs a hot-swappable battery design, enabling maintenance and replacements without interrupting power to critical systems. This ensures that organizations can maintain uptime while managing their UPS effectively.

The UPS is equipped with an advanced monitoring system that provides real-time visibility into power conditions and UPS performance. An intuitive graphical display allows users to easily track key metrics, while remote management capabilities ensure that the UPS can be monitored and controlled from anywhere, enhancing operational efficiency.

Safety features are paramount in the design of the APC 60-80KW UPS. It includes robust short-circuit protection and thermal management to prevent overheating and damage. Furthermore, the unit is compliant with various industry standards, ensuring reliable operation in a variety of environments.

In conclusion, the APC 60-80KW 208/480V UPS is a reliable, efficient, and advanced solution designed to safeguard crucial infrastructure against power interruptions. Its features, including modularity, dual input configurations, and intelligent monitoring, make it an ideal choice for organizations seeking to enhance their power reliability and operational effectiveness.