APC 60-80KW 208/480V UPS manual Set input switches Q001 to position

Page 15

Stop/Start UPS and Operating the External Service Bypass

Action

Display shows

 

1.Check that the output switch (Q004) is set to position 0

2.Check that all output switches (Q002) are set to position 1

3. Set input switches (Q001) to position 1

**System OFF**

4.Wait 10 secs.

Open the UPS front door and

press the green ON button on all systems

Normal operation

load power 0%

 

 

5. Press

on the keyboard

 

6.

Press

or

on the keyboard until

7.

Press

on the keyboard

8.Press on the keyboard

All systems switch to bypass operation

Note!

If Q002s are in position 0 off, only programmed systems will switch to bypass

9.Set the output switch (Q004) to position 1

10.Turn the bypass switch (Q003) to position 0

The following can be carried out on any UPS

11. Press

on the keyboard

12. Press

or

on the keyboard until

13. Press

on the keyboard

14. Press

on the keyboard

All the systems will transfer to normal operation

Bypass operation

: NO

Bypass operation

: YES

Bypass operation

Lamp indication on Bypass Panel

H002 and H004 light up

Green light (H003) above bypass switch lights up

The green lamps (H002) and (H004) are switched off, but (H003) is lit until normal operation.

Display shows

Bypass operation

: YES

Bypass operation

: NO

Normal operation

load power 0%

No lamps on the bypass panel are lit

 

990-4035

 

 

User Guide APC Silcon 60-80kW 208V/480V UPS

15

Image 15
Contents Copyright 2000 APC Denmark ApS APC Silcon 60-80kW 208/480V UPS User GuideSafety Symbols used in this manual User Guide APC Silcon 60-80kW 208V/480V UPSThank You Contents Introduction IntroductionDisplay Unit Stop/Start UPS and Operating the External Service Bypass Stop UPS for stand-byStart UPS from stand-by Switching off the UPS Stop UPS for complete power downUPS start-up Start UPS from complete power downSystem start-up now completed Bypassing the Single System UPS Operating the External Service Bypass Switch single systemsUPS YES Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Batt. load Batt. tank Display of Measured ValuesEconomy Mode Using the Remote DisplayParameter Settings Parameter SettingsParameter Settings Switching to Bypass Operation Programming KeysProgramming Example Load power xx% Mode Comments Alarms and EventsAlarms and Events Displaying the Alarm StackAlarms Description Action Possible AlarmsUnlock Rectifying Alarm Messages Correction of false alarm situations during service Parallel Operation AlarmsBattery Capacity Test Maintenance & TestingMaintenance & Testing Battery Monitoring TestUntil Warranty WarrantyAPC Silcon UPS Limited Factory Warranty APC Denmark How to Contact APCHow to Contact APC APC CorporateUser Guide APC Silcon 60-80kW 208V/480V UPS User Guide APC Silcon 60-80kW 208V/480V UPS

60-80KW 208/480V UPS specifications

The APC 60-80KW 208/480V Uninterruptible Power Supply (UPS) is a robust solution designed to ensure continuous power and protection for mission-critical systems and sensitive equipment in data centers and industrial environments. With its impressive capacity, this UPS provides reliable backup power, ensuring operational continuity by delivering clean and stable power to connected loads, even during power disruptions.

One of the standout features of the APC 60-80KW UPS is its dual input configuration, enabling it to operate on both 208V and 480V systems. This flexibility allows businesses to effortlessly integrate the UPS into their existing electrical infrastructure while maintaining high efficiency. The UPS’s modular design further enhances its adaptability, allowing users to scale power capacity as their business grows or adjusts to changing demands.

The system incorporates advanced technologies to optimize performance and energy efficiency. The use of high-efficiency power conversion techniques results in reduced energy consumption and lower operating costs, making this UPS an environmentally friendly choice. Additionally, it features a high power factor, which allows it to deliver more usable power to the load, reducing the total cost of ownership.

The APC 60-80KW UPS also includes an intelligent battery management system that maximizes battery life by monitoring and adjusting charging cycles. It employs a hot-swappable battery design, enabling maintenance and replacements without interrupting power to critical systems. This ensures that organizations can maintain uptime while managing their UPS effectively.

The UPS is equipped with an advanced monitoring system that provides real-time visibility into power conditions and UPS performance. An intuitive graphical display allows users to easily track key metrics, while remote management capabilities ensure that the UPS can be monitored and controlled from anywhere, enhancing operational efficiency.

Safety features are paramount in the design of the APC 60-80KW UPS. It includes robust short-circuit protection and thermal management to prevent overheating and damage. Furthermore, the unit is compliant with various industry standards, ensuring reliable operation in a variety of environments.

In conclusion, the APC 60-80KW 208/480V UPS is a reliable, efficient, and advanced solution designed to safeguard crucial infrastructure against power interruptions. Its features, including modularity, dual input configurations, and intelligent monitoring, make it an ideal choice for organizations seeking to enhance their power reliability and operational effectiveness.