Chapter 2 System Description

rectifier failure, rectifier self-protection, the red LED is on. Once the alarm is gone, the red LED goes off.

The controller of the PSE2500-A3 has two major functions:

I. Monitoring the system operation status

Inside PSE2500-A3 there is an AC sensor card, which can sample the AC input voltage. The sampled signal is sent into the controller for data processing. Once the input voltage is lower than the pre-set alarm level of the input low voltage, the controller reports an AC input under-voltage alarm. Likewise, if the input voltage is higher than the pre-set alarm level of the input high voltage, the controller reports an AC input over-voltage alarm.

The sampled DC output voltage signal is also sent into the controller. Once the output voltage is lower than the pre-set alarm level of the output low voltage, the controller will reports a DC Low alarm. Likewise, if the output voltage is higher than the pre-set alarm level of the output high voltage, the controller reports a DC output high alarm.

The rectifier communicates with the controller through RS485 bus. The working status of the rectifier is passed to the controller in this way. Once the rectifier has an alarm, the information is passed to the controller. The rectifier failure alarm includes: AC input failure, DC output failure, fan failure, output high, over temperature, and module shut-down.

II. Communicate with deamon systems

The controller supports China national standard protocol YD/T

1104-2001. User can apply this protocol to read system information or

2-4

Image 15
Contents PSE2500-A3 External PoE Power System Technical Support About This Manual Chapter ContentsConvention Description Convention Description BoldfaceEnvironmental Protection Table of Contents Engineering Maintenance and Troubleshooting Architecture and Configurations Description Standard ConfigurationIntroduction Description Standard Configuration 2PSE2500-A3 configuration Features3PSE2500-A3 configuration Overview System DescriptionCondition Fault Green Red2Front panel of the rectifier ControllerII. Communicate with deamon systems Monitoring the system operation statusRS485 Pin Definition RS232 Pin DefinitionAC Distribution Unit DC Distribution UnitPin Definition Safety Statements SafetyPSE2500-A3 External PoE Power System Safety Precautions PSE2500-A3 External PoE Power System Safety Introduction Installation and DebuggingSafety Physical Mounting 1Physical installation Installing RectifiersFrame Grounding 2Installing rectifiers3Frame grounding Load ConnectionsConnecting to AC utility/ AC grounding Powering on the DeviceInitial Start-up PSE2500-A3 External PoE Engineering Maintenance Troubleshooting Maintenance and TroubleshootingLED Indication Possible solution Controller Rectifier Possible Alarm Display Problems StatusRegulatory compliance standards Controller Rectifier PossibleDiscipline Standards