Guide Specification – 3-Phase Static Uninterruptible Power Supply

9.1.2HTTP Familiarity

The RemotEye II shall provide a HTTP interface for the UPS to allow easy access of the UPS information from any machine with a web browser. At any time, a network workstation or management station shall be able to open a RemotEye II website. RemotEye II website shall enable the UPS system information to be configured and monitored remotely. RemotEye II shall provide access to 3 java applets for monitoring, event logging, and trend analysis.

9.1.3Shutdown Capability

The RemotEye II application software shall allow RemotEye II to remotely notify and shutdown selected network servers.

Network Adapter/External Hardware

AMD 188ES-20MHz

512kB SRAM: 512kB Flash

Two asynchronous serial ports

10 BaseT RJ-45 connector

Toshiba UPS communication protocol

SNMP over UDP/IP : HTTP over TCP/IP:ARP, RARP, TFTP and

ICMP

MIB_II : Toshiba v1.2_MIB :JEM MIB : RFC 1628

Traffic LED for network : Status LED for status : Power LED for

Power

2 digit (default setting is Switches 1 and 2 off)

Temperature Range: 0 – 40 C

Relative Humidity: 10 – 80 %

Power Requirements: 12 VDC ungrounded

2.0 Watts Maximum

Dimensions: 5.28”(134mm) x 3.40”(86mm) x 1.10”(27mm) (LxWxH)

Weight: 0.38lbs(170g)

Certifications: FCC class A, UL, CUL, CE

9.2Remote Status Alarm Panel (RSAP)

The manufacturer shall optionally provide a RSAP that shall provide a wall-mounted LED mimic display for UPS status events of:

Input ON Bypass ON Inverter ON

Low Battery, AC Fail New alarm annunciation

Battery backup for the RSAP monitor.

15

Image 15
Contents Toshiba G9000 Page Table of Contents Remote Status Alarm Panel Rsap System Description ScopeGeneral Conditions for Installation System Parameters Page Functional Description Page Bypass Page Page Communications Optional WarrantyBattery Cabinets Option Mechanical DesignIcmp Auxiliary Transformer Cabinets Option Maintenance Bypass Panel OptionPower Distribution Units Option Toshiba Distribution Cabnet TDC OptionExtended Services Option