Guide Specification – 3-Phase Static Uninterruptible Power Supply

5.5.4Mimic Panel

A one-line diagram of the system shall be displayed on the touch panel display panel to provide a visual status of contactors within UPS. The panel shall display the followings:

AC Input, DC Input Rectifier in Operation Inverter in Operation UPS/Bypass supply

Battery Operating Condition (float charge/discharge) Fault, Warning

Operation Guidance (LCD Display) Fault Guidance (LCD Display)

5.5.5Isolated Control Signals

Normally Open isolated contact signal outputs for remote use will be furnished for the following operating status indications:

Summary Alarm Load on Bypass Load on Inverter Battery Operation Rectifier Operation Battery Low Voltage Overload

Total alarm

Output Contactor Closed

Contact rating:

Output: 1 A @ 30 VDC.

Input: 24 VDC

UPS module accepts remote switches to initiate the following remote operations. These contacts shall be field supplied):

Remote Start Remote Stop

Battery Temperature High Power Demand Emergency Power Off (EPO)

Contact rating:

Input: 24 VDC

The contact signal inputs and outputs shall be wired to a terminal block located inside the UPS.

13

Image 13
Contents Toshiba G9000 Page Table of Contents Remote Status Alarm Panel Rsap System Description ScopeGeneral Conditions for Installation System Parameters Page Functional Description Page Bypass Page Page Battery Cabinets Option WarrantyMechanical Design Communications OptionalIcmp Power Distribution Units Option Maintenance Bypass Panel OptionToshiba Distribution Cabnet TDC Option Auxiliary Transformer Cabinets OptionExtended Services Option