Guide Specification –
3.2.3 Clearances for installation |
|
Ceiling Level | : 20” minimum from top of UPS to ceiling |
Front | : 40” minimum for maintenance |
| (Local and regional codes may apply) |
Bottom | : Knockouts for power cable access |
Rear | : Zero clearance required |
Sides | : Zero clearance if using bottom cable access |
| (Standard knockouts for left/right side |
| cable access ) |
Base | : Channel mounted |
4SYSTEM PARAMETERS
4.1UPS Requirements:
4.1.1 General Requirements: |
|
|
Rated Output Capacity | : 80/100/160/225 kVA | |
| (72/90/144/202.5 kW) | |
AC/DC Rectifier Type | : AC/DC | |
DC/AC Inverter Type | :DC/AC | |
| Inverter |
|
External Dimensions | (W) (D) | (H)* |
80 kVA | : 27.6”x 32.8”x 78.7 (80.6)” | |
100 kVA | : 27.6”x 32.8”x 78.7 (80.6)” | |
160 kVA | : 35.4”x 32.8”x 78.7 (80.6)” | |
225 kVA | : 35.4”x 32.8”x 78.7 (80.6)” | |
| * Unit height with fan assembly installed | |
Weight |
|
|
80 kVA | : 855 lbs |
|
100 kVA | : 855 lbs |
|
160 kVA | : 1160 lbs |
|
225 kVA | : 1230 lbs |
|
Power Cable Access | : Bottom, Sides, Top Entry with optional | |
| side cabinet |
|
Paint Color | : Black (Munsell N1.5) | |
4.1.2 AC Input: |
|
|
Configuration | : | |
Rated Voltage | : 480V |
|
Voltage Variation | : +15% to |
|
Rated Frequency | : 60Hz |
|
Frequency Variation | : |
|
Input Power Factor | : Greater than 0.99 lagging at |
7