Guide Specification – 3-Phase Static Uninterruptible Power Supply

3.2.3 Clearances for installation

 

Ceiling Level

: 20” minimum from top of UPS to ceiling

Front

: 40” minimum for maintenance

 

(Local and regional codes may apply)

Bottom

: Knockouts for power cable access

Rear

: Zero clearance required

Sides

: Zero clearance if using bottom cable access

 

(Standard knockouts for left/right side

 

cable access )

Base

: Channel mounted

4SYSTEM PARAMETERS

4.1UPS Requirements:

4.1.1 General Requirements:

 

 

Rated Output Capacity

: 80/100/160/225 kVA

 

(72/90/144/202.5 kW)

AC/DC Rectifier Type

: AC/DC multi-level IGBT Rectifier

DC/AC Inverter Type

:DC/AC multi-level IGBT Inverter

 

Inverter

 

External Dimensions

(W) (D)

(H)*

80 kVA

: 27.6”x 32.8”x 78.7 (80.6)”

100 kVA

: 27.6”x 32.8”x 78.7 (80.6)”

160 kVA

: 35.4”x 32.8”x 78.7 (80.6)”

225 kVA

: 35.4”x 32.8”x 78.7 (80.6)”

 

* Unit height with fan assembly installed

Weight

 

 

80 kVA

: 855 lbs

 

100 kVA

: 855 lbs

 

160 kVA

: 1160 lbs

 

225 kVA

: 1230 lbs

 

Power Cable Access

: Bottom, Sides, Top Entry with optional

 

side cabinet

 

Paint Color

: Black (Munsell N1.5)

4.1.2 AC Input:

 

 

Configuration

: 3-Phase/3-Wire + Ground

Rated Voltage

: 480V

 

Voltage Variation

: +15% to –20%

 

Rated Frequency

: 60Hz

 

Frequency Variation

: +/-10%

 

Input Power Factor

: Greater than 0.99 lagging at 25%-115% load

7

Image 7
Contents Toshiba G9000 Page Table of Contents Remote Status Alarm Panel Rsap System Description ScopeGeneral Conditions for Installation System Parameters Page Functional Description Page Bypass Page Page Communications Optional WarrantyBattery Cabinets Option Mechanical DesignIcmp Auxiliary Transformer Cabinets Option Maintenance Bypass Panel OptionPower Distribution Units Option Toshiba Distribution Cabnet TDC OptionExtended Services Option