Toshiba G9000 manual

Page 12

Guide Specification – 3-Phase Static Uninterruptible Power Supply

If the bypass source is beyond the conditions stated below, interrupted transfer shall be made upon detection of a fault condition.

Bypass voltage greater than + 10%, -10% from the UPS rated output voltage. Bypass frequency greater than + 1 Hz from the UPS rated output frequency.

5.4.2Overload Capacity in Bypass:

Continuous duty

: 125% of the system rated capacity

Overload duty

: 1000% of ampere rating for 1 cycle.

5.4.3Retry function:

When an internal warning has been detected, power flow will automatically switch from the main circuit (inverter) to the bypass circuit without interruption to the load. If the internal warning is cleared, UPS will automatically switch the power flow from the bypass circuit to the main circuit (inverter) without interruption.

5.5Metering, Monitoring, Alarms, and Controls

5.5.1Status Indicators

The Front Panel shall include LED status indicators for the following states: Load on Inverter

Battery Operation Load on Bypass Overload

LCD Fault UPS Fault

5.5.2EPO (Emergency Power Off) Button

The Front Panel shall have an Emergency Power Off button (EPO) located on the front panel that, when pressed, will shut down the UPS.

5.5.3Liquid Crystal Display (LCD) Touch Panel

The Front Panel shall include a LCD touch panel that shall provide performance data, statistics, and operating conditions. The following metering will be displayed on LCD touch panel:

AC Input Voltage AC Input Frequency AC Output Voltage AC Output Current AC Output Frequency Battery DC Voltage Battery DC Current AC Bypass Voltage AC Bypass Frequency

12

Image 12
Contents Toshiba G9000 Page Table of Contents Remote Status Alarm Panel Rsap Scope System DescriptionGeneral Conditions for Installation System Parameters Page Functional Description Page Bypass Page Page Warranty Battery Cabinets OptionMechanical Design Communications OptionalIcmp Maintenance Bypass Panel Option Power Distribution Units OptionToshiba Distribution Cabnet TDC Option Auxiliary Transformer Cabinets OptionExtended Services Option