Guide Specification –
If the bypass source is beyond the conditions stated below, interrupted transfer shall be made upon detection of a fault condition.
Bypass voltage greater than + 10%,
5.4.2Overload Capacity in Bypass:
Continuous duty | : 125% of the system rated capacity |
Overload duty | : 1000% of ampere rating for 1 cycle. |
5.4.3Retry function:
When an internal warning has been detected, power flow will automatically switch from the main circuit (inverter) to the bypass circuit without interruption to the load. If the internal warning is cleared, UPS will automatically switch the power flow from the bypass circuit to the main circuit (inverter) without interruption.
5.5Metering, Monitoring, Alarms, and Controls
5.5.1Status Indicators
The Front Panel shall include LED status indicators for the following states: Load on Inverter
Battery Operation Load on Bypass Overload
LCD Fault UPS Fault
5.5.2EPO (Emergency Power Off) Button
The Front Panel shall have an Emergency Power Off button (EPO) located on the front panel that, when pressed, will shut down the UPS.
5.5.3Liquid Crystal Display (LCD) Touch Panel
The Front Panel shall include a LCD touch panel that shall provide performance data, statistics, and operating conditions. The following metering will be displayed on LCD touch panel:
AC Input Voltage AC Input Frequency AC Output Voltage AC Output Current AC Output Frequency Battery DC Voltage Battery DC Current AC Bypass Voltage AC Bypass Frequency