Guide Specification –
Harmonic Voltage Distortion | : < 2% THD (100% Linear Load) | |
| : < 5% THD (100% | |
Phase Displacement | : 1° Maximum at 100% load | |
Voltage Transients: |
|
|
100% Load Step Change | : | Maximum (Without battery assistance) |
Loss or Return of Input | : | Maximum |
Transfer from Bypass to Inverter : | ||
(At Bypass Rated Voltage) |
|
|
Recovery Time | : 1 cycle |
5FUNCTIONAL DESCRIPTION
The UPS shall protect the load against surges, sags, undervoltage, and voltage fluctuation. The UPS shall have
5.1IGBT Rectifier
5.1.1General
A
5.1.2Voltage Regulation
The rectifier output voltage shall not deviate by more than +/- 1.0% RMS under the following conditions:
0% - 100% loading (balanced and unbalanced loading,
+15% - 20% utility voltage change
5.1.3Reflected Harmonic Content Input current THD shall be
< 3% at
< 6% at
5.2IGBT
5.2.1General
A
5.2.2Battery Charge Current Limit
The Converter logic shall provide DC for controlled battery charging. The battery current sensing shall be independent of the Converter DC Output current sensing to provide precise battery recharging control. The DC/DC Charging Converter shall include a circuit to regulate the battery charging current to between 100% and 125%.
9