Siemens TPS3 15, TPS3 12 user manual Surge Current Rating TPS3, Option code / description TPS3

Page 6

Table 1: Model Number Decoder

 

 

 

TPS Series Description

 

 

 

 

 

 

 

 

 

 

 

TPS3 12

Externally mounted SPD, single module in enclosure, standard modes of protection

 

 

TPS3 L12

Externally mounted SPD, single module in enclosure, 10 modes of protection

 

 

TPS3 15

Externally mounted SPD, dual replaceable modules in enclosure, standard modes of protection

 

TPS3 L15

Externally mounted SPD, dual replaceable modules in enclosure, 10 modes of protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

available voltages

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Codes

 

 

TPS3 12

 

TPS3 L12

 

TPS3 15

TPS3 L15

 

 

 

 

 

 

 

 

A = 240/120V Split Phase 1Ø, 3W Plus Grnd (Fig 1)

 

 

 

B = 240/120V 3Ø, High Leg Delta (B High) (Fig 3)

 

 

 

C = 208Y/120V 3Ø, 4W Plus Grnd (Fig 2)

 

 

 

D = 240V 3Ø, 3W Plus Grnd (Fig4)

 

 

 

 

 

E = 480Y/277V 3Ø, 4W Plus Grnd (Fig 2)

 

 

 

F = 480V 3Ø, 3W Plus Grnd (Fig 4)

 

 

 

 

 

G = 600V 3Ø, 3W Plus Grnd (Fig 4)

 

 

 

 

 

K = 380Y/220V 3Ø, 4W Plus Grnd (Fig 2)

 

 

 

L = 600Y/347V 3Ø, 4W Plus Grnd (Fig 2)

 

 

 

 

 

S = 400Y/230V 3Ø, 4W Plus Grnd (Fig 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVALABLE SURGE CURRENT RATING

 

 

 

 

 

 

 

 

 

 

 

 

Surge Current Rating

 

TPS3 12

 

TPS3 L12

 

TPS3 15

TPS3 L15

 

 

 

 

 

 

 

 

 

10

= 100kA per phase

 

 

 

 

 

 

15

= 150kA per phase

 

 

 

 

20

= 200kA per phase

 

 

 

 

 

 

25

= 250kA per phase

 

 

 

 

 

 

30

= 300kA per phase

 

 

 

 

40

= 400kA per phase

 

 

 

 

 

 

45

= 450kA per phase

 

 

 

 

 

 

50

= 500kA per phase

 

 

 

 

 

 

60

= 600kA per phase

 

 

 

 

 

80

= 800kA per phase

 

 

 

 

 

 

90

= 900kA per phase

 

 

 

 

 

 

1K

= 1000kA per phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE OPTIONS (When Option is Not Selected Include a "0" in the Field)

 

 

 

 

 

 

 

 

 

 

option code / description

 

TPS3 12

 

TPS3 L12

 

TPS3 15

TPS3 L15

 

 

 

 

 

 

 

 

0 = Standard NEMA 1/12/3R/04 enclosure

 

 

 

V = NEMA 4X Non-metallic enclosure

 

 

 

S = NEMA 4X Stainless Steel enclosure

 

 

 

F = NEMA 1 Flush Mount enclosure

 

 

 

P = NEAM 1 Screwcover Pullbox enclosure

 

 

 

X = Surge Counter

 

 

 

 

D = Internal Rotary Disconnect Switch

 

 

 

 

 

T = Thru-door Rotary Disconnect Switch

 

 

 

Figure 1

 

}V

Hot (BLK)

 

 

 

}V

Neutral (WHT)

 

 

 

 

 

 

Hot (BLK)

 

 

 

Ground (GRN)

 

 

 

 

 

 

 

 

SPLIT

2 Hots, 1 Neu, 1 Grnd

Figure 2

Phase A (BLK)

A

B Phase B (BLK)

N }V

Neutral (WHT)

Phase C (BLK)

C

Ground (GRN)

WYE

3 Hots, 1 Neu, 1 Grnd

Figure 3

Phase A (BLK)

Phase B (ORNG)

V

}

Phase C (BLK)

Neutral (WHT)

Ground (GRN)

HI-LEG DELTA (B High)

3 Hots, (B HIGH),

1 Neu, 1 Grnd

Figure 4

 

V

Phase A (BLK)

}

 

 

Phase B (BLK)

 

Phase C (BLK)

 

Ground (GRN)

DELTA & HRG WYE 3 Hots, 1 Grnd

3

Image 6
Contents TPS3 12 & TPS3 Bonding and Grounding Hazard Table of Contents Limited Warranty IntroductionGeneral Information SPD TypesSurge Current Rating TPS3 Option code / description TPS3Pre-Installation and Planning Parallel ConnectionCircuit Breaker and Disconnect Switch Weight & DimensionsService Clearance Lead Lengths & Maximizing SPD PerformanceModule Rotation Feature TerminalsStep Grounding conductorTPS3 12 and TPS3 15 Installation Instructions Electrical Drawings Operation Shown with Surge CounterMaintenance Dry Contact Connection ConfigurationPage 17.11.jb #8172