Emerson 381333234 E manual Time Delay Adjustment, Sensor Adjustments, Time Delay Settings

Page 11

SECTION 4 ADJUSTMENTS

Time Delay Adjustment

Standard time delays are set to customer specifications (if none specified, standard factory settings are used).

To change a setting, follow procedure on page 4-2. Use Table 4-1 as a guide to time delay values and their corre- sponding adjustment DIP switch or potentiometer.

Table 4-1. Time Delay Settings

DESCRIPTION

LABELS

FACTORY ADJUSTMENT

SETTING RANGE

S3 DIP SWITCH

ADJUSTMENT

POTENTIOMETER

Override Momentary

TD ES

3 seconds

1 second

Actuator 1 on

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Source Outages

 

 

 

 

 

 

 

 

 

 

3 seconds

Actuator 1 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transfer to Emergency

TIMER

0 minutes

0 to 5

 

 

 

 

 

P2

N/E

(full ccw)

minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Override Momentary

4 seconds

non-adjustable

 

 

 

 

 

Emergency S. Outages

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Retransfer to Normal

TIMER

30 minutes

1 second to

 

 

 

 

 

P1

E/N

(full cw)

30 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unloaded Running

5 minutes

non-adjustable

 

 

 

 

 

(Engine Cooldown)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensor Adjustments

Voltage and frequency sensor pickup and dropout points are set to customer specifications (if none specified, standard factory settings are used). To change a setting, follow procedure on page 4–2. Use Tables 4-2 and 4–3 for settings and corresponding DIP switch actuators.

Table 4-2. Voltage and Frequency Settings. (

NOTICE

Any change in these settings may affect the normal operation of the automatic transfer switching equipment. This change could allow the load circuits to remain connected to a low voltage source.

Shaded DIP switches are standard factory settings).

DESCRIPTION

LABELS

SETTING

 

% of nominal

S1 DIP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FACT. SET

ADJ RANGE

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PU / N

Pickup

90 %

 

95 % *

Actuator 3 off

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90 %

Actuator 3 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90 % *

Actuator 1 off

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Source Voltage

 

 

 

 

 

Actuator 2 off

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Actuator 1 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85 %

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

DO / N

Dropout

85 %

 

Actuator 2 off

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80 %

Actuator 1 off

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Actuator 2 on

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70 %

Actuator 1 on

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Actuator 2 on

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Emergency Source Volt-

– –

Pickup

90 %

 

non-adjustable

– –

 

 

 

 

 

 

 

 

 

 

 

 

 

age

– –

Dropout

75 %

 

non-adjustable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– –

Pickup

95 %

 

non-adjustable

– –

 

 

 

 

 

 

 

 

 

 

 

 

 

Emergency Source

– –

Dropout

85 %

 

non-adjustable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60 Hz

Actuator 4 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

60 / 50

60 / 50 Hz

60 Hz

 

 

 

4

 

 

 

 

 

 

Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50 Hz

Actuator 4 on

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 phase

Actuator 6 off

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage Phases

3 4 , 1 4

3 4 / 1 4

 

3 4

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 phase

Actuator 6 on

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* If dropout voltage is set to 90%, the pickup voltage must be set to 95%.

Table 4-3. Transformer Voltage Adjust.

(Low setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V, or 480 V to 460 V)

DESCRIPTION

LABELS

FACTORY SETTING

ADJUSTMENT

S3 DIP SWITCH

Voltage Adjust (4.2%)

LOW /

HI

LOW

Actuator 2 off

 

 

 

 

 

HI

HI

Actuator 2 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 2

4--1

Image 11
Contents Nameplate / rating Label Operator’s Manual200 a Catalog Number IdentificationGrounding InstallationMounting Engine Starting Contacts InstallationPower connections Interconnecting harnessManual Operation Installation Functional TestVoltage Checks Electrical Operation Transfer To Emergency Sequence of OperationDisconnecting the Controller Testing & ServicePreventive Maintenance Check in Numerical Sequence Testing & ServiceTROUBLE-SHOOTING Manual Load TransferTime Delay Settings AdjustmentsTime Delay Adjustment Sensor AdjustmentsSW3 actuator On each DIP switch Off on AdjustmentsHow to Change a Setting SwitchesBUILT-IN Engine Exerciser Control Features Engine ExercisersDIP Switch Settings How to Set Built-In TimerOptional Programmable Engine Exerciser Accessory 11CD Control FeaturesChanging or Checking Time Programs Setting the Clock Time and DayCanceling Time Programs Programming Engine On-Off PeriodsLoad Disconnect Feature Remote Control FeaturesInphase Monitor For Motor Load Transfer Page Index