Emerson 381333234 E manual Remote Control Features, Inphase Monitor For Motor Load Transfer

Page 16

CONTROL FEATURES (continued)

INPHASE MONITOR

FOR MOTOR LOAD TRANSFER

Inphase monitoring logic controls transfer and retransfer of motor loads, so that inrush currents do not exceed normal starting currents. It avoids nuisance tripping of circuit breakers and mechanical damage to motor couplings.

The Motor Load Transfer feature is built into the controller. DIP switch S1 (actuator 5) activates this feature: right = ON, left = OFF.

FUNCTION

S1 DIP SWITCH

 

 

 

enable

Actuator 5 on

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

disable

Actuator 5 off

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shaded DIP switches are standard factory settings.

Note

If the Motor Load Transfer feature is enabled, it will be activated following the Load Disconnect Feature Delay Before Transfer delay.

LOAD DISCONNECT FEATURE

Connect external circuits to the terminals indicated on the Wiring Diagram provided with the ATSE.

The double throw (Form C) contact is rated for 28 VDC or 120 VAC (5 amps resistive). The contact operates prior to a selectable 0, 3, 10, or 20 second delay before transfer of the automatic transfer switching device. The contact resets either immediately following transfer or after the same delay as set for pre–signal before transfer.

Time delay between the load disconnect control signal and initiation of transfer is set on the controller with DIP switch S2 (actuators 6, 7, 8) as shown below:

Delay Before Transfer

LD TDBT

S2 DIP SWITCH

 

 

 

 

 

Actuator 7 on

 

 

 

 

 

 

 

 

 

 

0 (disable)

 

 

 

 

 

 

7

 

Actuator 8 on

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 seconds

Actuator 7 on

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

Actuator 8 off

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 seconds

Actuator 7 off

 

 

 

 

 

7

 

 

 

 

 

 

 

 

Actuator 8 on

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20 seconds

Actuator 7 off

 

 

 

7

 

 

 

 

 

 

 

 

Actuator 8 off

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shaded DIP switches are standard factory settings.

Delay After Transfer*

LD TDAT

S2 DIP SWITCH

enable

Actuator 6 on

 

 

 

 

disable

Actuator 6 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 6

*Enabling the Delay After Transfer will cause the control signal to reset after the same delay as set for the Delay Before Transfer.

REMOTE CONTROL FEATURES

These remote control features require a customer–supplied normally closed contact suitable for a 5 V dc low energy circuit. Refer to the Wiring Diagram provided with the ATS. Activate appropriate DIP switch S2 actuators below.

Remote Test (terminals CP6–7)

RTSW

S2 DIP SWITCH

disable

Actuator 3 on

 

 

 

 

enable

Actuator 3 off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 3

Remote Transfer to Emergency (CP8–9)

RT /E

S2 DIP SWITCH

 

 

 

disable

Actuator 2 on

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

enable

Actuator 2 off

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bypass Transfer Time Delay (CP12–13)

TD E/N BYP.

S2 DIP SWITCH

 

 

 

disable

Actuator 1 on

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

enable

Actuator 1 off

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inhibit Transfer to Emergency (CP10–11)

N/E INHIB.

S2 DIP SWITCH

 

 

 

disable

Actuator 4 on

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

enable

Actuator 4 off

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5--4

Image 16
Contents Operator’s Manual Nameplate / rating LabelCatalog Number Identification 200 aMounting InstallationGrounding Installation Power connectionsInterconnecting harness Engine Starting ContactsInstallation Functional Test Manual OperationVoltage Checks Electrical Operation Sequence of Operation Transfer To EmergencyPreventive Maintenance Testing & ServiceDisconnecting the Controller Testing & Service TROUBLE-SHOOTINGManual Load Transfer Check in Numerical SequenceAdjustments Time Delay AdjustmentSensor Adjustments Time Delay SettingsAdjustments How to Change a SettingSwitches SW3 actuator On each DIP switch Off onControl Features Engine Exercisers DIP Switch SettingsHow to Set Built-In Timer BUILT-IN Engine ExerciserControl Features Optional Programmable Engine Exerciser Accessory 11CDSetting the Clock Time and Day Canceling Time ProgramsProgramming Engine On-Off Periods Changing or Checking Time ProgramsInphase Monitor For Motor Load Transfer Remote Control FeaturesLoad Disconnect Feature Page Index