NOTICE

Do not make any setting changes while the controller is energized.

How to Change a Setting

1. Prevent the transfer switching device from operat-

ing by disconnecting one source first, then the

other, as follows:

a. If the transfer switching device is in the Normal

position, open the emergency source circuit

breaker. Turn the engine starting control to off.

Then open the normal source circuit breaker.

b. If the transfer switching device is in the

Emergency position, open the normal source

circuit breaker. Turn engine starting control to

cover

thumb

 

latch

hook on left side

Figure 4-1. Controller cover latch.

 

test or run. Then open the emergency source

 

circuit breaker.

2.

Disconnect both harness plugs from controller by

 

squeezing the latches. Do not pull on the wires.

3.

Remove cover from the controller by releasing latch

 

on right side with your thumb. See Figure 4-1.

4.

Locate the appropriate adjustment potentiometer or

 

DIP switch for the setting that you want to change.

 

Refer to Table 4-1 and Table 4–2 on page 4-1 and

 

Figure 4-2, Figure 4–3, Figure 4–4 on page 4–2.

5.

Use a small screwdriver to turn the potentiometer

 

clockwise to increase the time delay or counter-

 

clockwise to decrease it. See Figure 4-3.

harness plugs

S3 DIP switch

S1 DIP switch

S2 DIP switch

9 volt alkaline battery

J5 battery on/off jumper

P1 retransfer to normal time delay

P2 transfer to emergency time delay

6.

Use a ball-point pen (or similar pointed tool) to

 

slide the switch actuators left or right so they match

 

the illustration next to the setting (left = off, right =

 

on). Recheck the setting. See Figure 4-4.

7.

Install the cover on the controller by hooking it on

 

the left side and latching the right side.

8.

Reconnect both harness plugs to the controller by

 

aligning and pressing straight in until latches click.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Close the automatic transfer switching equipment enclosure door and tighten the screws before restoring power.

9.Close the enclosure door, then restore both sources:

a.If the transfer switching device is in the Normal position first close the normal source circuit breaker, then close the emergency source cir- cuit breaker.

b.If the transfer switching device is in the Emergency position, close the normal source circuit breaker. The load will be automatically retransferred to the normal source. Then close the emergency source circuit breaker.

10. Turn the engine starting control to automatic.

Figure 4-2. Location of potentiometers, DIP switches, battery, and battery jumper.

clockwise to increase

P1 or P2 potentiometer

counterclockwise to decrease

Figure 4-3. Changing time delay potentiometers.

DIP

switches

SW1

SW2

SW3 actuator

(8 on each DIP switch)

off on

Figure 4-4. Setting DIP switch actuators.

4--2

Image 12
Contents Operator’s Manual Nameplate / rating LabelCatalog Number Identification 200 aInstallation MountingGrounding Installation Power connectionsInterconnecting harness Engine Starting ContactsInstallation Functional Test Manual OperationVoltage Checks Electrical Operation Sequence of Operation Transfer To EmergencyTesting & Service Preventive MaintenanceDisconnecting the Controller Testing & Service TROUBLE-SHOOTINGManual Load Transfer Check in Numerical SequenceAdjustments Time Delay AdjustmentSensor Adjustments Time Delay SettingsAdjustments How to Change a SettingSwitches SW3 actuator On each DIP switch Off onControl Features Engine Exercisers DIP Switch SettingsHow to Set Built-In Timer BUILT-IN Engine ExerciserControl Features Optional Programmable Engine Exerciser Accessory 11CDSetting the Clock Time and Day Canceling Time ProgramsProgramming Engine On-Off Periods Changing or Checking Time ProgramsRemote Control Features Inphase Monitor For Motor Load TransferLoad Disconnect Feature Page Index