Liebert 350-500 VA user manual Guide to Status Indicators, Troubleshooting

Page 19

TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the PowerSure PST experiences a problem. Use this information to determine whether external factors caused the problem. See Troubleshooting Chart for suggested remedy.

Fault

Utility/Battery

Indicator

Indicator

Site Wiring

Fault Indicator

1.The Fault Indicator illuminates, indicating the UPS detected a problem.

2.An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for low battery and overload warning conditions.

3.Utility/Battery Indicator may be illumi- nated as a diagnostic aid to the operator, as shown below:

Guide to Status Indicators

Fault

Site Wiring

Utility/Battery

 

(Red)

Fault (Amber)

(Green)

Diagnosis/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Audible Alarm

!

 

 

 

 

+

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

UPS is operating in Normal

 

 

Mode; no beep.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashing

Battery Test has been initiated;

 

 

 

no beep.

Flashing

 

 

ON

Site Wiring Fault; no beep.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashing

 

 

ON

The unit is overloaded; beep

 

 

every half-second

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

ON

The UPS has failed;

 

 

continuous beep

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashing

 

 

 

Unit has shut down due to

 

 

 

overload; continuous beep

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

The UPS shut down due to

 

 

 

failure; continuous beep

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The UPS is operating in

Flashing Battery mode; beep every 5 seconds.

Flashing UPS battery is low; beep every half-second

Flashing

Flashing

The unit is overloaded; beep

every half-second

ON

Flashing

The UPS has failed;

continuous beep

15

Image 19
Contents PowerSure PST Page Table of Contents Page Safety Precautions Important Safety InstructionsPage Battery Handling Precautions Introduction and System Description Surge protection only Top and Side Views of UPSInverter Transfer SwitchBattery Charger BatteryWHAT’S Included Installation To Bottom for ionary Markings Controls and Indicators ON/OFF/Alarm Silence ButtonUtility/Battery Indicator Green Status Indicators Utility/Battery, FaultBattery Mode Normal ModeModes of Operation USB Interface Port Data Line Protection ConnectorsCommunications Maintenance Cleaning the UPSMaintaining Batteries Troubleshooting Guide to Status IndicatorsStart Troubleshooting ChartInput AC Parameters SpecificationsProduct Warranty Registration Battery Run TimesPage Company Behind the Products