SPECIFICATIONS

Model Number

PA350-120U

PA500-120U

Model Rating VA / W

350/225

500 / 300

DIMENSIONS: in (mm)

 

 

Unit W x D x H

6.6 x 9.8 x 3.7

6.6 x 9.8 x 3.7

(168 x 250 x 95)

(168 x 250 x 95)

 

Shipping W x D x H

9.4 x 13.8 x 5.6

9.4 x 13.8 x 5.6

(238 x 350 x 142)

(238 x 350 x 142)

 

WEIGHT: lbs (kg)

 

 

Unit

11.7 (5.3)

13.5 (6.1)

Shipping

12.1 (5.5)

13.9 (6.3)

INPUT AC PARAMETERS

 

 

 

Surge Protection

603J

 

Voltage Range Without

98VAC - 140VAC ±3VAC

Battery Operation

 

 

 

Frequency

57 - 63 Hz (±0.4Hz)

Input Power Cord

6.5 ft.attached, w/ NEMA 5-15 P

OUTPUT AC PARAMETERS

 

 

 

Output Receptacles

(3) NEMA 5-15R (orange) battery backup+surge protection

(2) NEMA 5-15R (black) surge protection

 

Voltage (Battery Mode)

120VAC ±8%

 

Output Current

2.9 A

 

4.2 A

Waveform (Battery Mode)

Stepped Sinewave

Frequency (Battery Mode)

60Hz ±1Hz

 

Overload Warning

>100%

 

Overload Shutdown

>110%

 

BATTERY PARAMETERS

 

 

 

Type

Valve-regulated, nonspillable, lead acid

Quantity x Voltage x Rating

1 x 12V x 5 Ah

 

1 x 12V x 7 Ah

Transfer Time

4 – 6 ms

typical

 

Back-up Time:

At 77°F (25°C), resistive loading, w/ fully charged batteries:

Full load

5 minutes

 

3 minutes

Half load

16 minutes

 

15 minutes

Recharge Time

12 hours to 90% capacity,

after full discharge into

resistive load

 

 

 

ENVIRONMENTAL

 

 

 

Operating Temperature

+32°F to + 104°F (0°C to +40°C)

Storage Temperature

+5°F to + 122°F (-15°C to +50°C)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000 m) at 86°F (30°C) w/o derating

Audible Noise

< 40 dBA, at 1 meter

AGENCY

 

 

 

Safety

UL 1778, c-UL Listed

Surge

ANSI C62.41, Category A, Level 3, (IEEE 587, Category A);

EN61000-4-5, Level 3, Criteria A

 

ESD

EN61000-4-2, Level 3, Criteria A

Susceptibility

EN61000-4-3, Level 2, Criteria A

Electrical Fast Transient/Burst

EN61000-4-4, Level 3, Criteria A

Emissions

FCC Part 15, Subpart B, Class B

Harmonics

EN61000-3-2

 

Conducted Immunity

EN61000-4-6

 

Flicker

EN61000-3-3

 

Transportation

ISTA Procedure 1A

17

Image 21
Contents PowerSure PST Page Table of Contents Page Safety Precautions Important Safety InstructionsPage Battery Handling Precautions Introduction and System Description Surge protection only Top and Side Views of UPSBattery Charger Transfer SwitchBattery InverterWHAT’S Included Installation To Bottom for ionary Markings Controls and Indicators ON/OFF/Alarm Silence ButtonUtility/Battery Indicator Green Status Indicators Utility/Battery, FaultNormal Mode Battery ModeModes of Operation Data Line Protection Connectors USB Interface PortCommunications Cleaning the UPS MaintenanceMaintaining Batteries Troubleshooting Guide to Status IndicatorsStart Troubleshooting ChartInput AC Parameters SpecificationsProduct Warranty Registration Battery Run TimesPage Company Behind the Products