MODES OF OPERATION
Normal Mode
During Normal mode operation, the Power- Sure PST supplies conditioned, computer- grade power to the connected equipment: util- ity power passes through the TVSS circuitry, EMI/RFI filters and then through the Trans- fer Switch to the connected equipment.
When the UPS is in Normal mode, the Utility/Battery Indicator illuminates green.
+-
Continuous LED
illumination denotes
Normal Mode
The PowerSure PST continuously monitors the batteries to maintain them in a fully charged state. The battery charger operates whenever AC power is present, even if the UPS is switched off. The UPS per- forms an automatic battery test after it has been operating continu- ously for two (2) weeks.
Battery Mode
The UPS switches to Battery mode in the event of an extreme voltage/frequency condi- tion or complete utility failure. The battery system supplies power through the Inverter to generate power for connected equipment. When the UPS is in Battery mode, the Utility/ Battery Indicator flashes green and an alarm sounds every 5 seconds.
+-
Flashing LED
illumination denotes
Battery Mode
When a low battery condition occurs, the Battery Indicator continues to flash green and the alarm sounds every
! CAUTION
Turning off the UPS while in either Normal mode or Battery mode will result in the loss of output power.
NOTE
Once utility power is restored, the UPS resumes normal operation. At this time, the battery charger begins recharging the battery. The UPS is capable of
12