PROGRAMMING ETHERNET DEVICES

PROGRAMMING ETHERNET DEVICES

This covers all of the steps needed to get the PRO22EN Ethernet Daughter board on-line and working. Programming of these units will be outlined within this Installation Guide.

PRO22EN Programming

The PRO22EN will be programmed from a Command Prompt using the ARP command. ARP (Address Resolution Protocol), a TCP/IP protocol used to convert an IP address into a physical address (called a DLC address), such as an Ethernet Address. A host wish- ing to obtain a physical address broadcasts an ARP request onto the TCP/IP network. The host on the network that has the IP address in the request then replies with its physical hardware address (MAC address).

EQUIPMENT NEEDED

1.PRO22IC (Intelligent Controller)

2.PRO22EN (Ethernet Card and Mounting Kit)

3.A Networked Computer.

4.A Network Crossover cable to connect directly to the PRO- 2200 or a Network Connection that is on the same network segment as the PRO-2200.

Special Note: When programming the Ethernet card verify that you’re not initially going through a gateway or a router. When programming is complete the unit can be installed on a different network segment.

HARDWARE SETUP

1.Prior to mounting the PRO22EN onto the PRO22IC verify the MAC address on the back of the PRO22EN (Ethernet Card). This address will be needed during programming of the card with the correct IP Address, Subnet Mask, and Gateway.

Example: MAC Address 00-20-4A-54-49-B7 MAC Address______________________________

Static IP Address___________________________

(Check with MIS\IT Department)

Subnet Mask _______________________________

(Check with MIS\IT Department)

Default Gateway_____________________________

(Check with MIS\IT Department)

Image 9
Contents Part Number PRO22EN PRO-2200 Ethernet Board Installation ManualTD1145 rev0601 Page Contents WARNINGS AND CAUTIONS Fire Safety and Liability NoticePage UNPACKING PROCEDURE DISCLAIMERProduct Liability Mutual Indemnification Shipping Instructions Limited WarrantyConfidentiality PROGRAMMING ETHERNET DEVICES HARDWARE SETUPPRO22EN Programming EQUIPMENT NEEDEDJumper PROGRAMMING THE ETHERNET CARD Click OK 6.Select Connect and Remote System Note The 1 is port10.Your Choice? Enter 0 for server configuration 8.Press Enter for Setup ModeType 1 Enter for Channel 1 configuration 18.Flow=02 Enter Flow Control Enabled20.Select Enter through the rest of the menus 19.Port Number=3001 Enter Winpak Pro uses portRemote IP Adr ---none ---,Port Connect Mode C0 Disconn ModeBattery PRO22EN Mounting DiagramLAN Card Connector Configuration Dip Switches S12700 Blankenbaker Pkwy, Suite Louisville, KY Honeywell Security & Data Collection