Honeywell PRO-2200 manual Jumper

Page 10
Jumper

2.Set the dipswitches on the PRO22IC (S1) to: Baud Rate is 38, 400 bps

Flow Control is ON

Panel Address is 1

S1

8

OFF (PASSWORD OFF)

7ON (BAUD RATE)

6 ON (BAUD RATE)

5 ON (FLOW CONTROL)

4

OFF

(PANEL ADDRESS)

3

OFF

(PANEL ADDRESS)

2

OFF

(PANEL ADDRESS)

1 ON (PANEL ADDRESS)

3.Set the jumpers on the PRO22IC

Jumper

J14

OFF

(NETWORK ENABLED)

J12

ON

(PORT 2 EOL ACTIVE)

J13

ON

(PORT 3 EOL ACTIVE)

J4

2 AND 3 ON

J5

2 AND 3 ON

J6

2 AND 3 ON

J9

ON

 

4.Mount the PRO22EN to the PRO22IC (Mounting instructions on Page 15)

5.Finish Installation of PRO-2200. Refer to Installation manuals

6.Connect the Networked Computer to the Ethernet Card using CAT5 cable.

Image 10
Contents PRO-2200 Ethernet Board Installation Manual Part Number PRO22ENTD1145 rev0601 Page Contents Fire Safety and Liability Notice WARNINGS AND CAUTIONSPage DISCLAIMER UNPACKING PROCEDUREProduct Liability Mutual Indemnification Limited Warranty Shipping InstructionsConfidentiality PRO22EN Programming HARDWARE SETUPPROGRAMMING ETHERNET DEVICES EQUIPMENT NEEDEDJumper PROGRAMMING THE ETHERNET CARD Note The 1 is port Click OK 6.Select Connect and Remote SystemType 1 Enter for Channel 1 configuration 8.Press Enter for Setup Mode10.Your Choice? Enter 0 for server configuration 18.Flow=02 Enter Flow Control EnabledRemote IP Adr ---none ---,Port 19.Port Number=3001 Enter Winpak Pro uses port20.Select Enter through the rest of the menus Connect Mode C0 Disconn ModeLAN Card Connector PRO22EN Mounting DiagramBattery Configuration Dip Switches S1Honeywell Security & Data Collection 2700 Blankenbaker Pkwy, Suite Louisville, KY
Related manuals
Manual 20 pages 9.1 Kb Manual 16 pages 41.44 Kb Manual 16 pages 15.65 Kb