Input Point Module (AFI5100)
1.9Recommended Cable Specifications
The following table outlines the cable recommended for connection of an inte- grated security system:
Communication |
|
|
|
| Recommended Cable Specifications |
| ||
Type | Core | Pairs | AWG | Stranding | Wire Type | Insulation | Shield | Jacket |
| ||||||||
RS485 | 4 | 2 | 28 | 7 x 36 | Tinned | Polyethylene | Aluminium foil- Polyester tape | PVC |
|
|
|
|
| Copper |
| / braided shield |
|
| 6 | 3 | 28 | 7 x 36 | Tinned | Polyethylene | Aluminium foil- Polyester tape | PVC |
|
|
|
|
| Copper |
| / braided shield |
|
| 8 | 4 | 28 | 7 x 36 | Tinned | Polyethylene | Aluminium foil- Polyester tape | PVC |
|
|
|
|
| Copper |
| / braided shield |
|
RS232 | 4 | 2 | 24 | 7 x 32 | Tinned | Polyethylene | Aluminium foil- Polyester tape | PVC |
|
|
|
|
| Copper |
| / no braid |
|
| 6 | 3 | 24 | 7 x 32 | Tinned | Polyethylene | Aluminium foil- Polyester tape | PVC |
|
|
|
|
| Copper |
| / no braid |
|
| 8 | 4 | 24 | 7 x 32 | Tinned | Polyethylene | Aluminium foil- Polyester tape | PVC |
|
|
|
|
| Copper |
| / no braid |
|
RS422 | 4 | 2 | 24 | 7 x 32 | Tinned | Polyethylene | Aluminium foil- Polyester tape | PVC |
|
|
|
|
| Copper |
| / no braid |
|
| 6 | 3 | 24 | 7 x 32 | Tinned | Polyethylene | Aluminium foil- Polyester tape | PVC |
|
|
|
|
| Copper |
| / no braid |
|
| 8 | 4 | 24 | 7 x 32 | Tinned | Polyethylene | Aluminium foil- Polyester tape | PVC |
|
|
|
|
| Copper |
| / no braid |
|
8 | 4 | 24 | Solid | Bare | Polyethylene | Unshielded | PVC | |
|
|
|
|
| Copper |
|
|
|
| 8 | 4 | 24 | 7 x 32 | Tinned | Polyethylene | Unshielded | PVC |
|
|
|
|
| Copper |
|
|
|
8 | 4 | 24 | Solid | Bare | Polyethylene | Aluminium foil- Polyester tape | PVC | |
|
|
|
|
| Copper |
| / no braid |
|
| 8 | 4 | 24 | 7 x 32 | Tinned | Polyethylene | Aluminium foil- Polyester tape | PVC |
|
|
|
|
| Copper |
| / no braid |
|
Power | 2 | 1 | 18 | 19 x 30 | Tinned | Polyethylene | Unshielded | PVC |
(12/24 V DC) |
|
|
|
| Copper |
|
|
|
The previous table provides a guideline for selecting an appropriate cable type only. Other cable types are also compatible with the system and can be used to achieve the same results.
1.10Programming and Firmware Download
The AFI5100 is programmed using the host software application via the ACC, or using the FLN Configurator Field Service Tool application. Please refer to the ap- propriate User’s Guide for more Information.
Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are made.