Input Point Module (AFI5100)
1.8LEDs
The following table describes the operation of the LEDs located on the AFI5100 :
LED | Brief Description |
POWER | The POWER led is illuminated when power has been applied to the device. |
ACTIVITY | The ACTIVITY led indicates that the AFI5100 is accessing information con- |
| tained in its internal database or performing a routine operation. |
| This LED also indicates whether the initial instruction set has been downloaded. |
| If power is applied and the LED blinks quickly, the AFI5100 instruction set (firm- |
| ware) needs to be downloaded. If the LED is blinking slowly, approximately |
| once per second, a firmware set has already been downloaded. |
Tx COMMS | The Transmission COMMS LED flashes when the IPM is sending data to the |
| ACC to which it has been connected (via an FLN). |
Rx COMMS | The Transmission COMMS LED flashes when the IPM is receiving data from |
| the ACC to which it has been connected (via an FLN). |
Inputs | The tricolor Input Port LEDs indicate the current status of the input port. See the |
| table below for an explanation of the colors. |
Outputs | Each Output Relay has a corresponding LED that is illuminated when the relay |
| is activated. |
Fire | The Fire LED is illuminated when Fire |
Each input LED may be in one of two states as indicated by color.
LED Color
Green
Orange
Input status | Fire |
|
Denotes input Normal: Closed | Denotes FOR Normal: Closed | |
Denotes input Normal: Open | Denotes FOR Normal: Open (alarm) |