Siemens AFI5100 installation manual Links and Jumpers

Page 9

Input Point Module (AFI5100)

1.7Links and Jumpers

The following table outlines the link settings for the AFI5100 :

Link

Description

Value

 

 

LK1, LK2

Links 1 and 2 are used to configure

To enable Normal

To enable En-

 

whether Fire Over-ride (FOR) will oper-

Mode:

 

hanced Mode:

 

ate in Enhanced FOR mode or Normal.

 

LK1

LK2

LK1 LK2

 

Enhanced mode also requires the

 

 

AMORL

 

 

LAMR ON

 

connection of a supervision circuit to

 

 

 

the Fire Over-ride Input.

N

 

 

 

 

 

OR

 

 

ROF

 

 

F

 

 

 

LK4, LK6

Links 4 and 6 control whether Fire

FOR operation

FOR operation

 

Over-ride (FOR) is enabled.

active:

 

ignored:

 

If the links are set to FOR operation,

 

LK4

LK6

LK4 LK6

 

activation of the FOR input will cause

ELB ANE

 

 

ELBA NE

 

the outputs to return to the NO position.

 

 

 

If the links are set to the off position,

ROF

 

 

ROF

 

FOR input will have no effect on the

 

 

 

state of the output relays.

 

 

 

 

LK3, LK5

These auxiliary links have been included for further enhancement of the system.

LK7

LK7 affects the reset action when the

LK7

 

 

 

RESET link (LK9) is set and the power

 

 

 

 

 

 

 

 

turned on.

 

 

 

 

 

See LK9 below for a description of how

 

 

 

 

 

to reset the unit.

 

 

 

 

 

 

If the jumper on Link 7 is set as shown,

 

 

it is set to “Full Reset” mode.

LK7

 

 

If the jumper on Link 7 is taken off, it is

 

 

set to “Partial Reset” mode.

LK8

This is a General Purpose links that has been included for further enhancement

 

of the system.

 

 

LK9

Memory Clear and Reset

 

 

 

Setting LK9 and turning the power off and on will reset the IPM. A full or partial

 

reset can be achieved by setting LK7 on or off.

 

 

If LK7 is set, the IPM will fully reset and any firmware loaded into the memory will

 

be erased. You will need to re-program the IPM with firmware again before it can

 

operate.

 

 

 

If LK7 has the jumper removed, the microcontroller will be rebooted but the firm-

 

ware will remain in memory.

 

 

LK10

EOL Termination (Bus)

RS485 BUS port

RS485 BUS port

 

This link allows the RS485 BUS com-

not terminated.

terminated.

 

munications channel to be terminated

LK10

LK10

 

in noisy or lengthy comms.

 

 

 

 

Note: Units located at the end of bus

EOL

EOL

 

lines only should have this link set.

 

 

 

 

LK11 – LK14

FOR Activation

LK11

LK12

 

These links allow FOR activation to be

 

FOR EN

 

 

enabled or disabled for each individual

 

 

 

 

 

relay output.

FOR DIS

 

 

Enabling Fire Override for a relay

 

 

 

 

 

means that when the FOR input is

In the above diagram LK11 (Relay 1) is

 

activated, the relay output switch to the

set to FOR Enabled and LK12

 

NO position.

(Relay 2) is set to FOR Disabled.

 

 

 

9

Siemens Building Technologies

 

 

 

Fire Safety & Security Products

 

 

02.2005

Image 9
Contents Installation manual Page Contents Page Product Description Product NumbersPrerequisites Expected Installation Time WiringMounting Instructions 287mm Input 1 Input Input 17 InputFor For OUTLinks and Jumpers LEDs PowerLED ActivityProgramming and Firmware Download Recommended Cable SpecificationsAWG PVCInput Point Module AFI5100 Page Document no. A24205-A335-B245