Opal Pro to Mod TCP
Output | AB Ethernet | Name | Description |
Words | IP |
|
|
(Polled) |
|
|
|
Word 1 | Input Word 0 | Status | Bit 0 – Ready to Run (drive is enable |
|
|
| and has 3 phase power) |
|
|
| Bit 1 |
|
|
| Bit 2 – Full On (starter is phased fully |
|
|
| on) |
|
|
| Bit 3 – Up to Speed (started is |
|
|
| phased fully on and the current is |
|
|
| below 105% of nameplate current as |
|
|
| set in 13.01) |
|
|
| Bit 4 – Reverse |
|
|
| Bit 5 – Jogging |
|
|
| Bit 6 – DC Injecting |
|
|
| Bit 7 – Faulted |
|
|
| Bit 8 – IOC Fault |
|
|
| Bit 9 – MOL Fault |
|
|
| Bit 10 – Phase Loss Fault |
|
|
| Bit 11 – Shear Pin Fault |
|
|
| Bit 12 – Shorted SCR Fault |
|
|
| Bit 13 – Heat Sink OT Fault |
|
|
| Bit 14 – Reserved |
|
|
| Bit 15 – Watch Dog Bit |
Word 2 | Input Word 1 | Current | 833 = 500% of motor name plate |
|
| Feedback | current as set in 13.01 |
Word 3 | Input Word 2 | Phase Angle | Amount of time phased on in |
|
| Actual | microseconds |
Parameter | AB Ethernet | Name | Description | |
| IP |
|
|
|
1.01 | Input Word 3 | Current | Current feedback in Amps | |
1.02 | Input Word 4 | L1 to L2 | Line 1 to Line 2 Voltage in Volts | |
|
| Voltage |
|
|
1.03 | Input Word 5 | L1 to L3 | Line 1 to Line 3 Voltage in Volts | |
|
| Voltage |
|
|
1.04 | Input Word 6 | L2 to L3 | Line 2 to Line 3 Voltage in Volts | |
|
| Voltage |
|
|
1.05 | Input Word 7 | DI Status | Digital input status | |
|
|
| Bit 0 – Start | |
|
|
| Bit 1 | – Stop |
|
|
| Bit 2 | – Jog |
|
|
| Bit 3 | – Reverse |
|
|
| Bit 4 | – Reset |
1.06 | Input Word 8 | Analog Input | Analog input value in Volts X 100 |
Page 11