Honeywell VR8304 Choose Gas Control Location, Install Piping to the Gas Control

Page 3

VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROL

Choose Gas Control Location

Do not locate the gas control where it may be affected by steam cleaning, high humidity, dripping water, corrosive chemicals, dust or grease accumulation, or excessive heat.

To ensure proper operation, follow these guidelines.

• Locate the gas control in a well ventilated area.

• Mount the gas control high enough above the

cabinet bottom to avoid exposure to flooding or

splashing water.

• Ensure the ambient temperature does not

exceed the ambient temperature ratings for each

component.

• Cover the gas control if the appliance is cleaned

DROP

PIPED

HORIZONTAL GAS

SUPPLY

GAS

CONTROL

3IN.

(76 MM)

MINIMUM

2

DROP

HORIZONTAL

GAS CONTROL

RISER

PIPED

GAS

SUPPLY

3 IN.

with water, steam, or chemicals or to avoid dust

and grease accumulation.

• Avoid locating the gas control where exposure to

corrosive chemical fumes or dripping water is

1

TUBING GAS

SUPPLY 2

(76 MM)

MINIMUM

likely.

Locate the gas control in the appliance vestibule on the gas manifold. In replacement applications, locate the gas control in the same location as the old gas control.

Install Piping to the Gas Control

GAS

CONTROL RISER

3 IN.

(76 MM)

MINIMUM

2

All piping must comply with local codes and ordinances or with the National Fuel Gas Code (ANSIZ223.1 NFPA No. 54), whichever applies. Tubing installation must comply with approved standards and practices.

1.Use new, properly reamed pipe free of chips. If tub- ing is used, ensure the ends are square, deburred and clean. All tubing bends must be smooth and without deformation.

2.Run a pipe or tubing to the gas control. If tubing is used, obtain a tube-to-pipe coupling to connect the tubing to the gas control.

3.Install a sediment trap in the supply line to the gas control. See Fig. 2.

1ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.

2CAUTION: SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING END CAP TO PREVENT GAS FROM FILLING THE WORK AREA. TEST

FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.

M3077A

 

Fig. 2. Install a sediment trap.

 

TWO IMPERFECT

 

THREADS

GAS CONTROL

 

PIPE

Install the Gas Control

1.Mount the gas control 0–90 degrees in any direction from the upright position of the gas control knob, including vertically.

2.Mount the gas control so that gas flow is in the direc- tion of the arrow on the bottom of the gas control.

3.Thread the pipe the amount shown in Table 5 for insertion into the gas control or adapter. DO NOT THREAD THE PIPE TOO FAR. Valve distortion or malfunction may result if the pipe is inserted too deeply into the gas control.

4.Apply a moderate amount of good quality pipe com- pound (DO NOT use Teflon tape) to the pipe only, leaving two end threads bare. On LP installations, use a compound resistant to LP gas. Refer to Fig. 3.

5.Remove the seals over the gas control inlet and outlet if necessary.

6.Connect the pipe to the gas control inlet and outlet. Use a wrench on the square ends of the gas control. If an adapter is used, place the wrench on the adapter rather than the gas control. Refer to Figs. 4 and 5.

Table 5. NPT pipe thread length (inches)

 

Thread pipe this

Maximum depth pipe

 

can be inserted into the

Pipe size

amount

control

318

9/16

3/8

 

 

 

1/2

3/4

1/2

 

 

 

3/4

13/16

3/4

 

 

 

THREAD PIPE THE AMOUNT

APPLY A MODERATE AMOUNT OF

SHOWN IN TABLE FOR

PIPE COMPOUND TO PIPE ONLY

INSERTION INTO GAS CONTROL

(LEAVE TWO END THREADS BARE).

 

M3075B

Fig. 3. Use a moderate amount of pipe compound.

PRESSURE REGULATOR

 

 

ADJUSTMENT

 

WIRING

(UNDER CAP SCREW)

 

 

TERMINALS (3)

 

 

INLET

 

OUTLET

PRESSURE

 

 

PRESSURE

TAP

 

 

TAP

 

 

INLET

 

OUTLET

 

 

PILOT OUTLET

RED

 

PILOT ADJUSTMENT

GAS CONTROL

(UNDER CAP SCREW)

RESET BUTTON

M1639C

 

KNOB

 

 

Fig. 4. Top view of gas control.

Connect Pilot Gas Tubing

1.Cut tubing to desired length and bend as necessary for routing to the pilot burner. Do not make sharp bends or deform the tubing. Do not bend tubing at gas control or pilot burner after compression fitting has been tightened, as this may result in gas leak- age at the connection.

2.Square off and remove burrs from the ends of tubing.

3

69-0625—03

Image 3
Contents Application SpecificationsConverting Between Natural and LP Gas InstallationInstall Adapters to Gas Control Using Adapters to Solve Swing Radius ProblemsConnect Pilot Gas Tubing Install Piping to the Gas ControlInstall the Gas Control Choose Gas Control LocationTurn on the System WiringGas Control Knob Settings Startup and CheckoutLimit Adjust the Pilot Burner Flame Check and Adjust Gas Input to Main BurnerPerform Gas Leak Test Check Safety and Shutdown Performance MaintenanceTurning off the Appliance ServiceAutomation and Control Solutions Instructions to the Homeowner

VR8304 specifications

The Honeywell VR8304 is a sophisticated and reliable gas valve designed for use in residential and commercial heating applications. This integrated system is primarily used in conjunction with gas-fired appliances such as furnaces, boilers, and water heaters, offering improved efficiency and performance.

One of the standout features of the VR8304 is its dual combination of safety and comfort, thanks to its electronic ignition and safety shutoff mechanisms. This gas valve is equipped with a built-in pilot safety system that ensures safe operation. In the event of a failure in the ignition system, the VR8304 automatically shuts off the gas flow, preventing any potential hazards.

The unit is designed for compatibility with natural gas or propane, making it versatile for various heating needs. It utilizes a robust solenoid-operated design, which enhances its responsiveness. The VR8304 also boasts a high heat capacity, allowing it to efficiently handle significant gas flow for both heating and domestic hot water applications.

One of the technological advancements found in the VR8304 is its adaptive control features. The valve can adjust the gas flow rate depending on the demand, which not only optimizes fuel efficiency but also enhances the comfort of the environment by maintaining consistent temperature levels.

Installation of the VR8304 is straightforward due to its compact size and intuitive design. It fits standard piping configuration, reducing the need for complex adjustments or modifications during installation. Furthermore, its durable construction ensures long-lasting performance, with resistance to common issues such as corrosion and wear.

Another important characteristic of the Honeywell VR8304 is its low operating pressure combined with extended operating range. This ensures effective operation across various environmental conditions and helps maintain system integrity over time.

Finally, the Honeywell VR8304 is backed by robust customer support and service options, ensuring users have access to assistance and information to maximize their system's efficiency and safety. In conclusion, the Honeywell VR8304 stands out as a highly efficient, durable, and versatile gas valve for any heating application. Its innovative features and technologies provide both safety and performance, making it a top choice among HVAC professionals and homeowners alike.