Emerson 5081T-FF/FI instruction sheet Engineering Specifications, Quick-Start

Page 23

ENGINEERING SPECIFICATIONS

QUICK-START

1.On the Remote, press PROG, NEXT, ENTER.

2.Use the arrow buttons to select COnduc (conductivity), nAOH (Sodium Hydroxide 0-15%), HCL (Hydrochloric Acid 0-16%), H2SO4L (Sulfuric Acid 0-30%), H2SO4H (Sulfuric Acid 95-99.99%), or CuSt (custom curve) mode. Press ENTER. If you chose CuSt, continue with step 3. If you chose COnduc or one of the prepro- grammed % concentration modes, skip step 3 and go to step 4.

3.If you selected CuST, you will see the Setup Custom screen. To move to the custom curve configuration menu, press ENTER. You will automatically return to this same Setup Custom screen after configuration is complete. To continue transmitter display programming, press NEXT in the Setup Custom screen.

4.Use the arrow keys to toggle temperature units between Celsius and Farenheit.

5.Press ENTER then RESET.

6.Press PROG, ENTER.

7.Use the arrow key to toggle t AutO to On or OFF to select using either the process temperature (tAutO = On) or a manual temperature (tAutO = OFF). Press ENTER. If you selected t AutO = OFF, you will be prompted to enter the manual temperature; use the arrow keys, then press ENTER.

8.If you selected CondUC in step 2, you will see a COMP (Temperature Compensation type) screen. Use the arrow keys to select desired temperature compensa- tion: LinEAr (linear) or nOnE (raw or uncompensated conductivity). Press ENTER. If you are in LinEAR mode, you can now enter a particular temperature slope (default is 2%/degC), then press ENTER to apply the slope.

9.Press RESET.

10.Press CAL, NEXT, NEXT, NEXT, ENTER.

11.Use the arrow buttons to enter the cell constant of the sensor. Press ENTER, then EXIT.

12.To “zero” the sensor in air, press CAL, NEXT, ENTER.

13.Hold the sensor in air to zero. Press ENTER, then EXIT.

14.If you are measuring % concentration (nAOH, HCL, H2SO4L, or H2SO4H) or custom curve (CuSt), quick start is complete; proceed to step 20.

15.If you are measuring conductivity (CondUC), then stan- dardize the sensor by placing the sensor in a solution of known conductivity value. Press CAL, ENTER.

16.Use the arrow buttons to enter the current conductivity value of the solution. Press ENTER.

17.Press RESET.

To reset transmiter to factory default settings:

1.Press PROGRAM, NEXT, NEXT, NEXT. The screen should say "dEFAULt". Press ENTER.

2.Use the arrow keys to toggle between nO (retain your configuration and calibration settings) and YES (restore factory default settings to all variables).

3.Press ENTER, then EXIT.

23

Image 23 Contents
Read this page Before Proceeding Essential InstructionsRecommended Sensors Physical SpecificationsTransmitter Specifications @ 25C Loop SpecificationsI T N E X T Infrared Remote Controller FigureProcess Display 25.0C 12.00mADiagnose Menu Program MenuCalibrate Menu Wiring Model 5081T-FF/FI WiringPower Wiring Wiring Through a Junction BOXRotating the Display InstallationInstallation Unpacking and InspectionPage Page Page Page Page Finishsilkscreen Black Epoxy Paint Baked 2X Full RModel FM REV aLabel Wiring1400298 a 1400298NON-HAZARDOUS Locations 14002841400284 Hazardous Classified LocationsCSA 140 125125 650 ±.015 Unclassified Area 1400285Hazardous Area 1400285Artwork is Sheet 2 No Change Without Baseefa Approval II 1 G 1180125 4X R Baseefa REV aFisco Exploded View of Model 5081-T-FF/FI Transmitter MaintenanceTransmitter Maintenance OverviewDescription QUICK-START Engineering SpecificationsTo reset transmiter to factory default settings Specifications subject to change without notice